Panasonic WH-SDF03E3E5 Series Design Handbook page 65

Hide thumbs Also See for WH-SDF03E3E5 Series:
Table of Contents

Advertisement

Name
Info-Text
BT Req.
Buffer temperature requirement
SW Req.
Service water requirement
Cool Req.
Cooling temperature requirement
Aquarea air / water heat pump – design handbook 07 / 2014
Operating state 4
The heat pump operates in maximum mode according to the configurable
target temperature values, as defined in the table below. The amount of
the increased requirement can be set for the individual consumers via
absolute target values. For example, the target temperature of the hot-
water tank in operating state 4 can be set to a fixed value between 40 °C
and 70 °C. The actual values can be set by the user, within the specified
limits. Values outside the min. / max. limits are not possible. The settings
for operating state 4 are listed in the following table.
Parameter
Terminal assignments
In order to use the Aquarea heat pumps in a smart grid, the HPM must
be assigned the input terminals (Inp1 and Inp2), which the electricity
provider can then use to influence the operating mode of the controller
(using the two signalling contacts). The controller connections that can
be used are terminals 17 – 26. After assigning the two input terminals
(Inp1 and Inp2) the "Smart Grid" function is active. An open connection
to the Ground reference potential is interpreted as "Off" and a closed
connection is interpreted as "On".
Extensions and external interfaces
"Smart Grid" function via the Heat Pump Manager
Setting range
Min.
Max.
30
70
40
70
5
20
Closed-loop control
Default
Unit
50
°C
50
°C
12
°C
65