1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing for Monobloc Air-to-Water Heatpump System (here after referred to as “Monobloc unit”). Electrical work and water installation works must be installed or serviced by a licensed electrician and licensed water system installer respectively.
Page 4
Must follow local national wiring standard, regulation and this installation instruction. Strongly recommended to make permanent connection to a circuit breaker. For WH-MDC09C3E8: - Power 1: Use approved 20A 4-poles circuit breaker with a minimum contact gap of 3.0mm.
Page 6
Item Unit Monobloc Unit Running Current Cooling: 3.4 Heating: 2.9 Back-up Heater: Max. Current/Max. Input Power A/kW Common ELCB to Heat Pump Tank Heater [1 Phase, 230V]: Max. Current/ A/kW 13.0/3.00 Max. Input Power Power Factor Cooling: 96 Heating: 95 Power factor means total figure of compressor and outdoor fan motor.
WH-MDC12C9E8 Item Unit Refrigerant System Performance Test Condition EUROVENT Cooling Capacity 10.00 BTU/h 34100 kcal/h 8600 2.78 kcal/hW 2.39 Heating Capacity 12.00 BTU/h 40900 kcal/h 10320 4.67 kcal/hW 4.02 Air Flow Cooling: 93.3 (3290) /min (ft /min) Heating: 80.0 (2830) Refrigeration Control Device Expansion Valve Refrigeration Oil...
Page 8
Item Unit Monobloc Unit Back-up Heater: Max. Current/Max. Input Power A/kW 13.0/9.00 Tank Heater [1 Phase, 230V]: Max. Current/ A/kW 13.0/3.00 Max. Input Power Power Factor Cooling: 97 Heating: 96 Power factor means total figure of compressor and outdoor fan motor. Power Cord Number of core Length...
WH-MDC14C9E8 Item Unit Refrigerant System Performance Test Condition EUROVENT Cooling Capacity 11.50 BTU/h 39200 kcal/h 9890 2.61 kcal/hW 2.25 Heating Capacity 14.00 BTU/h 47800 kcal/h 12040 4.50 kcal/hW 3.87 Air Flow Cooling: 97.8 (3450) /min (ft /min) Heating: 84.0 (2970) Refrigeration Control Device Expansion Valve Refrigeration Oil...
Page 10
Item Unit Monobloc Unit Back-up Heater: Max. Current/Max. Input Power A/kW 13.0/9.00 Tank Heater [1 Phase, 230V]: Max. Current/ A/kW 13.0/3.00 Max. Input Power Power Factor Cooling: 97 Heating: 96 Power factor means total figure of compressor and outdoor fan motor. Power Cord Number of core Length...
WH-MDC16C9E8 Item Unit Refrigerant System Performance Test Condition EUROVENT Cooling Capacity 12.20 BTU/h 41600 kcal/h 10490 2.54 kcal/hW 2.19 Heating Capacity 16.00 BTU/h 54600 kcal/h 13760 4.23 kcal/hW 3.64 Air Flow Cooling: 97.8 (3450) /min (ft /min) Heating: 90.0 (3180) Refrigeration Control Device Expansion Valve Refrigeration Oil...
Page 12
Item Unit Monobloc Unit Starting Current Running Current Cooling: 7.2 Heating: 5.7 Back-up Heater: Max. Current/Max. Input Power A/kW 13.0/9.00 Tank Heater [1 Phase, 230V]: Max. Current/ A/kW 13.0/3.00 Max. Input Power Power Factor Cooling: 97 Heating: 96 Power factor means total figure of compressor and outdoor fan motor. Power Cord Number of core Length...
3. Features Inverter Technology - Energy saving High Efficiency Compact Design Environment Protection - Non-ozone depletion substances refrigerant (R410A) Easy to use remote control Weekly Timer setting Quality Improvement - Random auto restart after power failure for safety restart operation - Gas leakage protection - Prevent compressor reverse cycle - Inner protector to protect compressor...
4.1.1 Main Components Water Pump: The pump circulates the water in the water circuit. Pressure Gauge: The manomater allows read out of the water pressure in the water circuit. Flow Switch: The flow switch checks the flow in the water circuit and protects the heat exchanger against high pressure built-up and the pump against damage.
11.1 Select the Best Location 11.2 Mono Bloc Unit Installation Install Mono bloc unit at outdoor only. Mono bloc unit will become heavy when filled with Avoid location where ambient temperature is water. Therefore, please install the Mono bloc unit on below -20°C.
Make sure to use two spanners to tighten the connection. Further tighten the nuts with torque wrench in specified torque as stated in the table. Nut size (Torque) Model Water WH-MDC09C3E8 WH-MDC12C9E8 RP 1 1/4" [117.6 N•m] WH-MDC14C9E8 WH-MDC16C9E8 ...
In case of a power supply failure or pump operating failure, drain the system (as suggested in the figure below). When water is idle inside the system, freezing up is very likely to happen which could damage the system. Drainage piping installation ...
Page 43
Receiver shall be connected to “Room Thermostat”, refer to “Field Supply Accessories” table for details. Receiver’s cable must be (4 or 3 × min 0.5 mm ), double insulation layer of PVC-sheathed or polychloroprene sheathed cable. (connection refer to Diagram 4.2). Tank OLP’s cable must be (2 ×...
Page 44
11.4.1 Wire Stripping And Connecting Requirement Diagram 4.3: External Controller connecting diagram Diagram 4.2: Room Thermostat (Receiver) connecting diagram 11.4.2 Connecting Requirement For WH-MDC09C3E8: The equipment’s power supply 1 complies with IEC/EN 61000-3-2. The equipment’s power supply 2 complies with IEC/EN 61000-3-2.
Page 45
11.4.3 Wired Remote Controller 4 Installation WARNING 1. Be sure to turn off the main power before installing and connecting the remote controller. Otherwise, it will cause the electrical shock. 2. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, fire or electrical shock. 3.
Page 46
Embed an outlet box (JIS C 8336) into the wall. Outlet box may be purchased separately. Medium- sized square outlet box (obtain locally) Part No. DS3744 (Panasonic Co., Ltd.) or equivalent. Secure the remote controller lower case to the outlet box with the two accessory screws (3). Make sure that the lower case is fl at against the wall at this time, with no bending.
Page 47
B. IF REMOTE CONTROLLER CABLE IS EXPOSED Install the remote controller lower case to the Route the remote controller cable (2) inside the wall with the two accessory screws (4). lower case in accordance with the intended Fasten the screws properly until screw head is feeding-out direction.
12. Operation and Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Page 49
12.1.4 Cool Mode Operation 3 ways valve control: 3 ways valve switch and fix to room side. Heatpump operate follow normal cooling operation. Backup heater DOES NOT operate during cool mode. Solar 3 way valve operates follow solar operation specification. 2 ways valve control: 2 ways valve is closed.
Page 50
12.1.5 Cool + Tank Mode Operation 12.1.6 Tank Mode Operation Control contents: 3 ways valve direction - 3 ways valve switch and fix to tank side. Heatpump Thermostat characteristic - Water set temperature = tank set temperature or [55°C] whichever lower. - Heatpump Water Outlet set temperature is set to Maximum (55°C) at tank mode i.
Page 51
ii. Case 2 - Heatpump THERMO OFF TEMP: Heatpump THERMO OFF TEMP = 55°C + [+2°C]. Water outlet temperature > Heatpump THERMO OFF TEMP for continuous 3 minutes, heatpump OFF but water pump ON. - Heatpump THERMO ON TEMP: Heatpump THERMO ON TEMP = Water inlet during thermo off time + [-3°C]. Heatpump ON back when water outlet temperature <...
Page 52
Solar Priority is Set Solar Priority is Not Set...
Page 53
12.1.7 Heat + Tank Mode Operation Setting 1: When Heating priority is set by control panel: 3 ways valve control: 3 ways valve switch and fix to room side. Heatpump operation control: Heatpump operate follow normal operation. Backup Heater control: Backup heater operate follow normal operation.
Page 54
Case 2: Heatpump THERMO OFF TEMP: 1. Heatpump THERMO OFF TEMP = 55°C + [+2°C]. 2. Water outlet temperature > Heatpump THERMO OFF TEMP for continuous 90 seconds, switch 3 ways valve to room side. End Tank heat-up interval and start count heating heat-up interval. THERMO ON TEMP: 1.
Page 55
Heat + Tank (Heating No Priority) (Solar Priority Set)
Page 56
Heat + Tank (Heating No Priority) (Solar Priority Not Set)
Page 57
12.1.8 Setting Water Outlet Temperature for Heat Mode The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit. Where by the internal water setting temperature is determined automatically depending on the outdoor temperature. The colder outdoor temperatures will result in warmer water and vice versa. The user has the possibility to shift up or down the target water temperature by remote control setting.
Page 58
12.1.8.1 Heating Mode Operation Time Chart Exp: 3 ways valve control: 3 ways valve switch and fix to room side. Heatpump operate follow normal heating operation. Backup heater operate follow normal operation. Solar 3 way valve operates follow solar operation specification. 2 ways valve control: 2 ways valve opens.
Page 59
12.1.9 Water Temperature Thermo Shift Setting Switchs are ignored during “PUMPDW” = ON. Switchs are ignored during “STATUS” = ON. ▲ ▼ “ ”, “ ”, “SELECT” switch are ignored if “SETTING” = OFF. “CANCEL” switch is ignored if “SETTING” = OFF & “STATUS” = OFF. ...
12.2 Water Pump 12.2.1 Water Pump Control Once the Monobloc unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes. However, during this 9 minutes operation, if there is any abnormality cause at Monobloc unit or malfunction, the compressor should be OFF immediately and restart delay after 3 minutes.
12.5 Force Heater Mode Operation The backup heater also serves as backup in case of malfunctioning of the Monobloc unit. Make sure the OFF/ON control panel LED is OFF (no operation). Press the Force button to start the force heater mode operation. During force heater mode, all other operations are not allowed.
12.8 Indication Panel Operation Color Green Light ON Operation ON Light OFF Operation OFF Note: If Operation LED is blinking, there is an abnormality operation occurs. 12.9 Back-Up Heater Control 12.9.1 Electric Heater Control Normal Heating Mode Heater On condition: a.
12.10 Tank Booster Heater Control 12.10.1 Tank Booster Heater Control Heating operation condition: Booster heater Turn On condition: After BOOSTER HEATER DELAY TIMER fulfil during heatpump startup time in tank mode, or during switching from heating heat-up interval to tank heat-up interval in heat+tank mode (heating priority not set).
12.14 Solar Operation (Optional) 12.14.1 Solar Operation Control according to preset whether solar priority is set or not. When tank connection is NOT set at SETTING mode, solar operation is disabled. When Pump A (from solar pump station) is detected On through connection Y3 and Y4, then the Solar pump 3 Way Valve is requested ON (Refer to figure below).
Page 65
Heat + Tank Mode (Heating Priority Not Set) (Solar Priority Set) (Solar Priority Not Set)
Page 66
Heat + Tank Mode (Heating Priority Set) Tank Mode (Solar Priority Set) (Solar Priority Not Set)
12.16 Two ways valve control Functionality of 2 ways valve: Use to allow hot water to floor heating panel or block cold water to floor heating panel. Control contents: When indoor running in heat mode, OPEN the 2 ways valve. When indoor running in cool mode, CLOSE the 2 ways valve.
13. Protection Control 13.1 Protection Control for All Operations 13.1.1 Time Delay Safety Control The compressor will not start for three minutes after stop of operation. 13.1.2 30 Seconds Forced Operation Once the compressor starts operation, it will not stop its operation for 30 seconds. However, it can be stopped using remote control.
Page 70
13.1.6 Low Frequency Protection Control 1 When the compressor continuously operates at frequency lower than 25 Hz for 240 minutes, the operation frequency will change to 24 Hz for 2 minutes. 13.1.7 Low Frequency Protection Control 2 When all the below conditions comply, the minimum compressor frequency will change to lower frequency. Temperature, T, for: Heating Cooling...
13.2 Protection Control for Heating Operation 13.2.1 Outdoor Air Temperature Control The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid compressor overloading. 13.2.2 Deice Operation When Monobloc unit (Refrigerant System) pipe temperature and outdoor air temperature is low, deice operation start where Monobloc unit fan motor stop.
14. Servicing Mode 14.1 Test Run Fill up the boiler tank with water. For details refer to boiler tanks installation instruction and operation instruction. Antifreeze agent must be added into water circuit to prevent freezing of water when outdoor ambient temperatures is low.
15. Maintenance Guide In order to ensure optimal performance of the unit, checks and inspections on the unit and the field wiring must be carried out regularly. Please request a licensed technician for carry out maintenance job. Before carried out any maintenance or repair work, and removing the front plate of heat exchanger unit, always switch off all power supply (i.e.
Page 74
How to release the trapped air in water circuit Turn up the lever to become horizontal. (Refer to figure “Pressure relief valve”). The trapped air will be drained out together with water. After few seconds, turn down the lever to stop the water drainage. Repeat it until the bubbling sound disappear.
16. Troubleshooting Guide 16.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table on the right.
16.2 Relationship between the Condition of the Monobloc Unit and Pressure and Electric Current Heating Mode Cooling Mode Condition of the Low Pressure High Pressure Electric current Low Pressure High Pressure Electric current Monobloc unit during operation during operation Water leakage or insufficient water flow rate in the system Excessive amount of...
16.3 Breakdown Self Diagnosis Function 16.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code) When abnormality occur during operation, the system will stop operation, and OFF/ON remote control LED will blink and error code will display on the remote control Timer display LCD. ...
16.4 Error Codes Table Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify No abnormality detected — — Indoor/Outdoor capacity unmatched 90s after power supply Indoor/outdoor connection wire Indoor/outdoor PCB Specification and combination table in catalogue ...
Page 79
Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify Voltage at PFC PFC control 4 times occurrence within 10 minutes Outdoor heat exchanger temperature Continue for 5 sec. Outdoor heat exchanger temperature sensor abnormality sensor (defective or disconnected) Outdoor defrost sensor abnormality Continue for 5 sec.
16.5 Self-diagnosis Method 16.5.1 Connection Capability Rank Abnormality (H12) Malfunction Decision Conditions: During startup operation of cooling and heating, the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality. Malfunction Caused: Wrong model interconnected. Wrong indoor unit or outdoor unit PCB (main) used.
Page 81
16.5.2 Compressor Tank Temperature Sensor Abnormality (H15) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the compressor tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 82
16.5.3 Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
16.5.4 Compressor Low Pressure Protection (H42) Malfunction Decision Conditions: During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or above 26°C is detected by the outdoor pipe temperature sensor. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit.
Page 84
16.5.5 Water Flow Switch Abnormality (H62) Malfunction Decision Conditions: During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to determine water flow error. Malfunction Caused: Faulty water pump. Water leak in system. Faulty connector connection.
Page 85
16.5.6 Outdoor High Pressure Abnormality (H64) Malfunction Decision Conditions: During operation of cooling and heating, when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 4 times in 20 minutes.
Page 86
16.5.7 Indoor Backup Heater OLP Abnormality (H70) Malfunction Decision Conditions: During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit. Malfunction Caused: Faulty power supply connector connection. Faulty connector connection. Faulty indoor backup heater overload protector (OLP). Faulty indoor unit PCB (main).
Page 87
16.5.8 Tank Temperature Sensor Abnormality (H72) Malfunction Decision Conditions: When tank connection is set to ON, the temperatures detected by the tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 88
16.5.9 Indoor-Remote Control Communication Abnormality (H76) Malfunction Decision Conditions: During standby and operation of cooling and heating, indoor-remote control error occur. Malfunction Caused: Faulty connector connection. Faulty remote control. Faulty indoor unit PCB (main).
Page 89
16.5.10 Indoor/Outdoor Abnormal Communication (H90) Malfunction Decision Conditions: During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused: Faulty outdoor unit PCB (main). Faulty indoor unit PCB (main). Indoor-outdoor signal transmission error due to wrong wiring.
Page 90
16.5.11 Tank Booster Heater OLP Abnormality (H91) Malfunction Decision Conditions: During operation of tank booster heater, and tank booster heater OLP open circuit. Malfunction Caused: Faulty connector connection. Faulty tank booster heater overload protector (OLP). Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 60 seconds.
Page 91
16.5.12 Unspecified Voltage between Indoor and Outdoor (H95) Malfunction Decision Conditions: The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused: Insufficient power supply. Faulty outdoor unit PCB (noise filter/main).
Page 92
16.5.13 Outdoor High Pressure Protection (H98) Malfunction Decision Conditions: During operation of heating, when pressure 4.0MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2/3 way closed.
Page 93
16.5.14 Indoor Freeze-up Protection (H99) Malfunction Decision Conditions: During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2 way valve partially closed. Clogged expansion valve or strainer.
Page 94
16.5.15 Outdoor High Pressure Switch Activate (F12) Malfunction Decision Conditions: During operation of cooling and heating, when pressure 4.5MPa and above is detected by outdoor high pressure switch. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit. Faulty water pump.
Page 95
16.5.16 Compressor Rotation Failure (F14) Malfunction Decision Conditions: A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused: Compressor terminal disconnect. Faulty outdoor unit PCB (main). Faulty compressor. Abnormality Judgment: Continue 4 times in 20 minutes.
Page 96
16.5.17 Outdoor Fan Motor (DC Motor) Mechanism Locked (F15) Malfunction Decision Conditions: The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused: Operation stop due to short circuit inside the fan motor winding.
Page 97
16.5.18 Input Over Current Detection (F16) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor current above 10.6A is detected by the current transformer (CT) in the outdoor unit PCB. Malfunction Caused: Excessive refrigerant. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 20 minutes.
Page 98
16.5.19 Compressor Overheating (F20) Malfunction Decision Conditions: During operation of cooling and heating, when temperature above 112°C is detected by the compressor tank temperature sensor. Malfunction Caused: Faulty compressor tank temperature sensor. 2/3 way valve closed. Refrigerant shortage (refrigerant leakage). Clogged expansion valve or strainer.
Page 99
16.5.20 IPM Overheating (F22) Malfunction Decision Conditions: During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature sensor. Malfunction Caused: Faulty outdoor unit fan motor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 30 minutes.
Page 100
16.5.21 Output Over Current Detection (F23) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor DC current is above 40.1 ± 5.0A (for: UD07~09CE) OR 44.7 ± 5.0A (for:UD12~16CE) is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main). Malfunction Caused: Faulty outdoor unit PCB (main).
Page 101
16.5.22 Refrigeration Cycle Abnormality (F24) Malfunction Decision Conditions: During operation of cooling and heating, compressor frequency > Frated. During operation of cooling and heating, running current: 0.65A < I < 1.65A. During operation of cooling, water inlet temperature - indoor refrigerant liquid temperature < 5°C. During operation of heating, indoor refrigerant liquid temperature - water inlet temperature <...
Page 102
16.5.23 Four Way Valve Abnormality (F25) Malfunction Decision Conditions: During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C. During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C. Malfunction Caused: Faulty sensor.
Page 103
16.5.24 Outdoor High Pressure Switch Abnormal (F27) Malfunction Decision Conditions: During compressor stop, and outdoor high pressure switch is remain opened. Malfunction Caused: Faulty connector connection. Faulty switch. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 1 minute.
Page 104
16.5.25 Outdoor Air Temperature Sensor Abnormality (F36) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 105
16.5.26 Indoor Water Inlet Temperature Sensor Abnormality (F37) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 106
16.5.27 Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 107
16.5.28 Power Factor Correction (PFC) Abnormality (F41) Malfunction Decision Conditions: During operation of cooling and heating, when the PFC protection circuitry in the outdoor unit PCB (main) senses abnormal high DC voltage level. Malfunction Caused: Power supply surge. Compressor windings not uniform. Faulty outdoor unit PCB (main).
Page 108
16.5.29 Outdoor Pipe Temperature Sensor Abnormality (F42) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 109
16.5.30 Outdoor Defrost Temperature Sensor Abnormality (F43) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 110
16.5.31 Indoor Water Outlet Temperature Sensor Abnormality (F45) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 111
16.5.32 Outdoor Current Transformer Open Circuit (F46) Malfunction Decision Conditions: A current transformer (CT) open circuit is detected by checking the compressor running frequency ( rated frequency) and CT detected input current (< 0.65A) for continuously 20 seconds. Malfunction Caused: CT defective.
Page 112
16.5.33 Cooling High Pressure Overload Protection (F95) Malfunction Decision Conditions: During operation of cooling, when pressure 4.0MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Dust accumulation in the outdoor unit heat exchanger. Air short circuit at outdoor unit. 2 way valve closed.
17. Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. WARNING Be sure to switch off all the power supply before performing each of the below action.
17.6 To Remove Transformer and Electronic Controller Board 17.7 To Remove Pressure Relief Valve When reinstall the water pipe, use grease or water at the joining.
17.8 To Remove Flow Switch When reinstall the water pipe, use grease or water at the joining. 17.9 To Remove Water Pump When reinstall the water pipe, use grease or water at the joining.
18. Technical Data 18.1 Operation Characteristics 18.1.1 WH-MDC09C3E8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C...
Page 119
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C...
Page 120
18.1.2 WH-MDC12C9E8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C...
Page 121
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C...
Page 122
18.1.3 WH-MDC14C9E8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C...
Page 123
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C...
Page 124
18.1.4 WH-MDC16C9E8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C...
Page 125
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C...
19. Exploded View and Replacement Parts List 19.1 WH-MDC09C3E8 WH-MDC12C9E8 WH-MDC14C9E8 WH-MDC16C9E8 (Refrigerant System)
Page 130
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 131
< Model: Refrigerant System> REF. DESCRIPTION & NAME QTY. WH-MDC09C3E8 WH-MDC12C9E8 WH-MDC14C9E8 WH-MDC16C9E8 REMARKS CWD52K1251 ← ← ← BASE PAN ASS’Y 5JD420XBA22 ← ← ← COMPRESSOR BUSHING - COMPRESSOR CWH50055 ← ← ← MOUNT CWH561049 ← ← ← NUT-COMPRESSOR MOUNT CWB811017 ←...
Page 132
REF. DESCRIPTION & NAME QTY. WH-MDC09C3E8 WH-MDC12C9E8 WH-MDC14C9E8 WH-MDC16C9E8 REMARKS CWB141055 ← ← ← RECEIVER G0C153J00009 ← ← ← REACTOR CWG87C2030 ← ← ← ACCESSORY CO.(DRAIN ELBOW) DADDG1010000 ← ← ← PTC THERMISTOR Note: All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
Page 134
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 135
< Model: Water System> REF. NO. DESCRIPTION & NAME QTY. WH-MDC09C3E8 WH-MDC12C9E8 WH-MDC14C9E8 WH-MDC16C9E8 REMARKS ← ← ← BASE PAN ASS’Y CWD52K1242 ← ← ← HOT WATER COIL-COMPLETE CWB90C1046 ← ← ← RECEIVER CWB141039 ← ← ← FLOAT (FLOW SWITCH) CWB601008 ←...