Panasonic WH-SDF03E3E5 Series Design Handbook page 122

Hide thumbs Also See for WH-SDF03E3E5 Series:
Table of Contents

Advertisement

Appendix
Heating capacity in relation to supply water and outside temperature
Aquarea LT
Outside temperature
-15
-7
2
7
25
-15
-7
2
7
25
-15
-7
2
7
25
-15
-7
2
7
25
Heating capacity [kW] of individual models of the monobloc system for different supply water and outside temperatures [°C].
122
Supply water temperature
30
35
40
8 .7
8 .0
8 .0
9 .4
9 .1
8 .9
9 .3
9 .0
9 .0
9 .0
9 .2
9 .0
9 .0
9 .0
8 .7
30
35
40
9 .3
8 .9
8 .5
10 .4
11 .1
9 .6
11 .8
11 .9
11 .0
12 .0
12 .2
12 .0
12 .0
12 .0
11 .8
30
35
40
9 .9
9 .8
9 .0
11 .1
11 .8
10 .2
12 .9
12 .7
11 .9
14 .0
14 .1
14 .0
14 .0
14 .0
14 .0
30
35
40
10 .6
10 .1
10 .0
11 .9
11 .4
10 .8
13 .5
12 .7
12 .4
16 .0
15 .8
16 .0
16 .0
16 .0
16 .0
45
50
55
7 .8
7 .2
6 .7
8 .7
8 .0
7 .1
9 .0
8 .3
8 .8
9 .0
9 .0
8 .0
8 .5
8 .3
8 .1
45
50
55
8 .1
7 .5
7 .0
9 .2
8 .7
8 .2
10 .6
9 .8
9 .1
12 .0
12 .0
12 .0
11 .7
11 .5
11 .4
45
50
55
8 .6
7 .9
7 .3
9 .8
9 .1
8 .5
11 .4
10 .4
9 .5
14 .0
13 .6
13 .3
14 .0
14 .0
14 .0
45
50
55
9 .7
8 .8
7 .9
10 .3
9 .6
7 .8
11 .9
10 .8
9 .8
15 .9
15 .2
14 .3
16 .0
16 .0
15 .9
Aquarea air / water heat pump – design handbook 07 / 2014
Models
9 kW (three phase)
WH-MDF09C3E8
WH-MDC09C3E8
12 kW (three phase)
WH-MDF12C9E8
WH-MDC12C9E8
14 kW (three phase)
WH-MDF14C9E8
WH-MDC14C9E8
16 kW (three phase)
WH-MDF16C9E8
WH-MDC16C9E8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-sdc03e3e5 seriesWh-sdf05e3e5 seriesWh-sdc07f3e5 seriesWh-sdc09f3e5 seriesWh-sdc09f3e8 seriesWh-sdc05e3e5 series ... Show all

Table of Contents