Carrier AQUASNAP 30RAP010-150 Controls, Start-Up, Operation, Service, And Troubleshooting page 89

Air-cooled chillers with puron refrigerant (r-410a)
Table of Contents

Advertisement

SUB-MODE
DISP
SH.SP
UNIT
MAX.T
FN.SQ
CSB.E
PM.P.S
PM.SL
PM.DY
OPT1
PM.DT
PMP.O
PM.HT
CND.T
MOPS
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory
ITEM
DISPLAY
TEST
ON/OFF
METR
ON/OFF
LANG
X
PAS.E
ENBL/DSBL
PASS
XXXX
SIZE
SZA.1
XX
SZA.2
XX
SZA.3
XX
SZB.1
XX
SZB.2
XX
SZB.3
XX
XX
FAN.S
X
EXV
YES/NO
A1.TY
YES/NO
XX
YES/NO
FLUD
X
MLV.S
YES/NO
ENBL/DSBL
CPC
ON/OFF
PM1E
YES/NO
PM2E
YES/NO
YES/NO
X
XX MIN
XXXX HRS
ROT.P
YES/NO
X
XX.X F
EMM
YES/NO
X
XX
APPR
XX
ITEM DESCRIPTION
DISPLAY CONFIGURATION
Test Display LEDs
Metric Display
Language Selection
Password Enable
Service Password
UNIT CONFIGURATION
Unit Size
Compressor A1 Size
Compressor A2 Size
Compressor A3 Size
Compressor B1 Size
Compressor B2 Size
Compressor B3 Size
Suction Superheat Setpt
Number of Fans
EXV Module Installed
Compressor A1 Digital
Maximum A1 Unload Time
YES, if unit produced on or after 2214
(WWYY)
NO, if unit produced before 2214
(WWYY)
UNIT OPTIONS 1 HARDWARE
Cooler Fluid
Minimum Load Valve Select
Csb Boards Enable
Cooler Pump Control
Cooler Pump 1 Enable
Cooler Pump 2 Enable
Cooler Pmp Periodic Strt
Cooler Pump Select
Cooler Pump Shutdown Dly
Pump Changeover Hours
Rotate Cooler Pumps Now
Cooler Pump Operation
Pump High Temp Cut Off
EMM Module Installed
Cnd HX Typ:0=RTPF 1=MCHX
EXV MOP Set Point
Config Approach Set Point
89
COMMENT
Off = English On = Metric
Default: 0
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
Default: Enable
Default: 1111
Automatically configured
dependant on unit size.
Default: 9 F
Dependent on Unit Size
Default: Yes
Default: No
Default: 7
Max = 12 (010,015)
Max = 10 (018-150)
Fan control logic/contactor
wiring changed
Default: Water
1 = Water
2 = Medium Temperature Brine
Default: No
Default: Enable
Default: Off
Default: No
Default: Automatic
0 = Automatic
1 = Pump 1 Starts first
2 = Pump 2 Starts first
0 to 10 minutes, Default: 1 min.
Default: 500 hours
User Entry
Default: 0
0 = Auto
1 = Continuous
Default: 95 F
Range: 95 - 125 F
EMM is automatically configured
to Yes when an option requiring
the EMM is configured.
Default: 50 F
Range: 40 - 80 F
Default: 9.0 F
Range: 5 - 40 F

Hide quick links: