APPENDIX D — BACNET COMMUNICATION OPTION (cont)
POINT DESCRIPTION
Fan Relay 1
Fan Relay 2
Fan Relay 3
Fan Relay 4
Fan Relay 5
Fan Relay 6
Fan Relay 7
Fan Relay 8
Head Setpoint
Heat Request
High SCT Circuit A
High SCT Circuit B
High Temperature Cooling
Ice Done
Ice Setpoint
Lead Pump
Lead/Lag Circuit Select
Lead/Lag Leaving Fluid
Leaving Fluid Temp - Prime
Variable
Loading Sequence Select
Low Cooler Suction Temp A
Low Cooler Suction Temp B
Low Sound Active
Low Sound Mode
Low Temperature Cooling
Machine Operating Hours
Machine Starts
Making ICE
Master/Slave Control
Minimum Comp. On Time
Minimum Load Valve Relay
Minimum OFF Time Active
Minutes Off Time
Occupancy Status
Outside Air Temperature
Override Modes in Effect
Percent Available Cap.
Percent Available Cap.
Percent Total Capacity
Percent Total Capacity
Percent Total Capacity
Pump 1 Maintenance Done
Pump 1 Run Hours
Pump 1 Service Countdown
Pump 2 Maintenance Done
Pump 2 Run Hours
Pump 2 Service Countdown
Pump Changeover Hours
Pump Off Delay Time
Pump Service Interval
Ramp Load Limited
Requested Stage
Rotate Cooler Pumps Now
LEGEND
R
— Read
W — Write
Table G — Network Points List (cont)
READ/
POINT NAME
UNITS
WRITE
FAN_1
R
FAN_2
R
FAN_3
R
FAN_4
R
FAN_5
R
FAN_6
R
FAN_7
R
FAN_8
R
HSP
R
°F
HEAT_REQ
R
MODE_21
R
MODE_22
R
MODE_18
R
ICE_DONE
R
CSP3
R/W
°F
LEADPUMP
R
LEAD_TYP
R
DUAL_LWT
R
°F
LWT
R
°F
SEQ_TYPE
R
MODE_7
R
MODE_8
R
LSACTIVE
R
MODE_25
R
MODE_17
R
HR_MACH
R
hr
CY_MACH
R
MODE_19
R
MODE_3
R
MODE_23
R
MLV_RLY
R
MODE_10
R
DELAY
R/W
min
OCC
R
OAT
R/W
°F
MODE
R
CAPA_A
R
%
CAPB_A
R
%
CAP_T
R
%
CAPA_T
R
%
CAPB_T
R
%
P1_MAINT
R/W
HR_PUMP1
R
hr
P1_CDOWN
R
hr
P2_MAINT
R/W
HR_PUMP2
R
hr
P2_CDOWN
R
hr
PMP_DLTA
R/W
hr
MODE_24
R
SI_PUMPS
R/W
hr
MODE_5
R
STAGE
R
ROT_PUMP
R/W
DEFAULT
RANGE
VALUE
32.0
-20 - 32
1 = Automatic
2 = Pump 1
3 = Pump 2
4 = No Configuration
1 = Automatic
1
2 = Circuit A Leads
3 = Circuit B Leads
0
0 - 15
No
Yes/No
No
Yes/No
500
10 - 2000
8760
0 - 65535
No
No/Yes
121
BACNET
BACNET
OBJECT ID
OBJECT NAME
BV:60
fan_1_1
BV:61
fan_2_1
BV:62
fan_3_1
BV:63
fan_4_1
BV:64
fan_5_1
BV:65
fan_6_1
BV:66
fan_7_1
BV:67
fan_8_1
AV:29
hsp_1
BV:28
heat_req_1
BV:47
mode_21_1
BV:48
mode_22_1
BV:44
mode_18_1
BV:27
ice_done_1
AV:55
csp3_1
MSV:9
leadpump_msv_1
AV:43
lead_typ_1
AV:32
dual_lwt_1
AV:7
lwt_1
AV:77
seq_type_1
BV:35
mode_7_1
BV:36
mode_8_1
BV:2
lsactive_1
BV:51
mode_25_1
BV:43
mode_17_1
AV:57
hr_mach_1
AV:58
cy_mach_1
BV:45
mode_19_1
BV:32
mode_3_1
BV:49
mode_23_1
BV:79
mlv_rly_1
BV:38
mode_10_1
AV:42
delay_1
BV:2008
occ_status
AV:1003
oat_1
BV:5
mode_1
AV:12
capa_a_1
AV:22
capb_a_1
AV:3
cap_t_1
AV:11
capa_t_1
AV:21
capb_t_1
BV:52
p1_maint_1
AV:75
hr_pump1_1
AV:46
p1_cdown_1
BV:53
p2_maint_1
AV:76
hr_pump2_1
AV:47
p2_cdown_1
AV:39
pmp_dlta_1
BV:50
mode_24_1
AV:48
si_pumps_1
BV:33
mode_5_1
AV:9
stage_1
BV:12
rot_pump_1