CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION
COOLING RESET
Cooling Reset Type
4-20 MA RESET
4-20 – Degrees Reset
REMOTE RESET
Remote – No Reset Temp
Remote – Full Reset Temp
Remote – Degrees Reset
RETURN TEMPERATURE RESET
Return – No Reset Temp
Return – Full Reset Temp
Return – Degrees Reset
DEMAND LIMIT
Demand Limit Select
Demand Limit at 20 mA
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Switch 1
Demand Limit Switch 2
CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings)
DESCRIPTION
LEAD/LAG
Lead/Lag Chiller Enable
Master/Slave Select
Slave Address
Lead/Lag Balance Select
Lead/Lag Balance Delta
Lag Start Delay
Parallel Configuration
APPENDIX B — CCN TABLES (cont)
VALUE
0 = No Reset
1 = 4-20 mA input
2 = External temp – OAT
3 = Return Fluid
4 = External temp - SPT
–30 to 30
0 to 125
0 to 125
–30 to 30
0 to 125
0 to 125
–30 to 30
0 = None
1 = External switch input
2 = 4-20 mA input
3 = Loadshed
0 to 100
0 to 99
0 to 60
0 to 120
0 to 100
0 to 100
VALUE
Enable/Dsable
Master/Slave
0 to 239
0 = None
40 to 400
0 to 30
Yes
104
DEFAULT
UNITS
0
0.0
125.0
0.0
0.0
10.0
0.0
0.0
0
100
0
0
60
80
50
DEFAULT
UNITS
Dsable
Master
2
0
168
hours
5
minutes
Yes
POINT NAME
CRST_TYP
F
420_DEG
F
REM_NO
F
REM_FULL
F
REM_DEG
F
RTN_NO
F
RTN_FULL
F
RTN_DEG
DMD_CTRL
%
DMT20MA
SHED_NUM
%
SHED_DEL
minutes
SHED_TIM
%
DLSWSP1
%
DLSWSP2
POINT NAME
LL_ENA
MS_SEL
SLV_ADDR
LL_BAL
LL_BAL_D
LL_DELAY
PARALLEL