Solar/Group "4 - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Table of Contents

Advertisement

Code 2
DHW/group "3"
(cont.)
Coding in the delivered condition
65:0
Do not adjust
67:40
For solar DHW heating: set DHW
temperature 40 °C. Reheating is
suppressed above the selected set
temperature: boiler only starts as
backup if the rise in the DHW tem-
perature is too low.
6F:...
Max. heating output for DHW heat-
ing in %, specified by the coding
card
71:0
DHW circulation pump: "ON" ac-
cording to time program (only for
weather-compensated control
units)
72:0
DHW circulation pump: "ON" ac-
cording to time program (only for
weather-compensated control
units)
73:0
DHW circulation pump: "ON" ac-
cording to time program (only for
weather-compensated control
units)

Solar/group "4"

Select "Solar" for weather-compensated control unit
(see page 58).
Select "4" for constant temperature control unit (see
page 58).
Coding
Coding in the delivered condition
00:8
Start temperature differential for
solar circuit pump 8 K
01:4
Stop temperature differential for
solar circuit pump 4 K
02:0
Solar circuit pump is not speed-
controlled
03:10
Temperature differential for the
start of speed control 10 K
04:4
Controller amplification of the
speed control 4 %/K
66
Possible change
63:14
63:15
2 x daily
67:0
Set DHW temperature adjustable
to
from 0 to 95 °C (limited by boiler-
67:95
specific parameters)
6F:0
Max. heating output for DHW heat-
to
ing adjustable from min. heating out-
6F:100
put to 100 %
71:1
"OFF" during DHW heating to set
value 1
71:2
"ON" during DHW heating to set val-
ue 1
72:1
"OFF" during DHW heating to set
value 2
72:2
"ON" during DHW heating to set val-
ue 2
73:1
"ON" from once per hour for 5 min
to
up to 6 times per hour for 5 min dur-
73:6
ing the time program
73:7
Constantly "ON"
Note
The solar group is only displayed if a solar control
module, type SM1, is connected.
Possible change
00:2
Start temperature differential adjust-
to
able from 2 to 30 K
00:30
01:1
Stop temperature differential adjust-
to
able from 1 to 29 K
01:29
02:1
Solar circuit pump is speed-control-
led with wave packet control
02:2
Solar circuit pump is speed-control-
led with PWM control
03:5
Temperature differential adjustable
to
from 5 to 20 K
03:20
04:1
Controller amplification adjustable
to
from 1 to 10 %/K
04:10