Checking The Fuse; Extension Kit, Mixer - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Table of Contents

Advertisement

Troubleshooting
Maintenance
(cont.)
3. Press reset button R and repeat commissioning.
The check is repeated until it is completed success-
fully.

Checking the fuse

A
Fig.53
1. Switch off the power.
2. Release the side closures and pivot the control unit
down.

Extension kit, mixer

Checking the setting of rotary selector S1
The rotary selector on the PCB of the extension kit
defines the assignment to the relevant heating circuit.
Heating circuit
Heating circuit with mixer M2
(Heating circuit 2)
Heating circuit with mixer M3
(Heating circuit 3)
Checking the rotational direction of the mixer
motor
After being switched on, the boiler implements a self-
test. During this, the mixer is opened and closed again.
92
F1
3. Remove cover
4. Check fuse F1 (see connection and wiring dia-
Note
The mixer motor can also be started via the actuator
test (see chapter "Checking outputs").
Note the rotational direction of the mixer motor during
its self-test.
Rotary selector S1
Then set the mixer manually to "Open" again.
setting
2
Note
The flow temperature sensor must now capture a
4
higher temperature. If the temperature drops, either
the motor is turning in the wrong direction or the mixer
insert is incorrectly fitted.
.
A
gram).
Mixer installation instructions