Troubleshooting
Fault codes
(cont.)
Displayed
Const.
fault code
EF
X
F0
X
F1
X
F2
X
F3
X
F6
X
F8
X
F9
X
FA
X
FC
X
88
Weather-
System characteris-
comp.
tics
X
Burner in a fault state Flame is lost imme-
X
Burner blocked
X
Burner in a fault state Flue gas tempera-
X
Burner in a fault state Boiler water tem-
X
Burner in a fault state Flame signal is al-
X
Burner in a fault state Boiler water tem-
X
Burner in a fault state Fuel valve closes
X
Burner in a fault state Fan speed too low
X
Burner in a fault state Fan idle state not
X
Burner in a fault state Gas train faulty,
Cause
Measures
Check gas supply (gas
diately after it has
pressure and gas flow
built (during the
switch).
safety time).
Check balanced flue sys-
tem for flue gas recircula-
tion.
Check ionisation elec-
trode (replace if required):
Distance to burner
gauze assembly (see
page 36)
Electrode contamination
Press reset button R.
Internal fault
Replace control unit.
Check heating system fill
ture has exceeded
level. Vent the system.
limit.
Press reset button R after
flue system has cooled
down.
Check heating system fill
perature sensor
level. Check circulation
has responded.
pump. Vent the system.
Check boiler water tem-
perature sensor and con-
necting cables.
Press reset button R.
Check ionisation elec-
ready present at
trode and connecting ca-
burner start.
ble.
Press reset button R.
Replace boiler water tem-
perature sensor
perature sensors
temperature values
vary too widely
from one another.
Check gas train. Check
too late.
both control paths.
Press reset button R.
Check fan, fan connecting
during burner start
cables and power supply;
check fan control.
Press reset button R.
Check fan, fan connecting
reached
cables and fan control.
Press reset button R.
Check gas train. Check
faulty modulation
flue system.
valve control or
Press reset button R.
flue gas path
blocked