Fan Motor (Dc Motor) Or Related Abnormality - Daikin CTXU25G2V1B Service Manual

Inverter multi system with humidifying
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

Troubleshooting
2.9

Fan Motor (DC Motor) or Related Abnormality

A6
Remote
Controller
Display
Method of
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Malfunction
Detection
Malfunction
When the detected rotation speed does not reach the demanded rotation speed of the target
tap, and is less than 50% of the maximum fan motor rotation speed.
Decision
Conditions
Supposed
Causes
123
Operation halt due to short circuit inside the fan motor winding.
Operation halt due to breaking of wire inside the fan motor.
Operation halt due to breaking of the fan motor lead wires.
Operation halt due to faulty capacitor of the fan motor.
Detection error due to faulty indoor unit PCB.
SiBE12-908
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ctxu35g2v1b2mxu40gv1bCtxu42g2v1b2mxu50gv1bCtxu50g2v1b

Table of Contents