Damper Abnormality - Daikin CTXU25G2V1B Service Manual

Inverter multi system with humidifying
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

SiBE12-908

2.24 Damper Abnormality

H1
Remote
Controller Display
Method of
Detected by the limit switch (LS) in the humidifier unit.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Service Diagnosis
Limit switch does not turn on or off when the operation of humidifier unit starts or finishes.
For example, when turning on the power supply, when humidification operation (including air
supply ventilation) starts.
Faulty damper operation due to frost
Faulty damper operation due to foreign material
Limit switch fault (including improper connection)
Defective motor for damper
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the damper fixed
due to frost?
NO
Is the wire connection
of limit switch (LS)
loosen?
NO
YES
Heat the damper unit and
melt frost
Is the damper fault
repeated?
YES
YES
Troubleshooting
NO
OK
(Check intake air and
humidifier unit for direct
sucking of moisture.)
Reconnect wires.
Replace the limit switch or
replace the outdoor unit
PCB.
(R10339)
142