Four Way Valve Performance Check - Daikin CTXU25G2V1B Service Manual

Inverter multi system with humidifying
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

SiBE12-908

3.14 Four Way Valve Performance Check

Check No.31
< Caution on resetting the power supply >
∗ Be sure to wait for 30 sec. or more after turning off the power supply.
(Fig. 1)
Service Diagnosis
Turn off the power and turn it on
again.
S80 voltage at
DC 0 V with
outdoor unit on?
YES
Start the heating operation.
S80 voltage at DC 130-230
V for 3 sec. after
compressor starts, and
then at about DC 12 ~15V
after that? (Fig. 1)
YES
Disconnect the four way valve coil
from the connector and check the
continuity.
Four way valve
coil resistance at
300 ~ 600 Ω ?
YES
Voltage at S80
3 sec.
DC180-280V
DC12~15V
Compressor
ON
NO
∗ Four way valve coil
Cooling / dry : No continuity
Heating : Continuity
NO
NO
Time
Check
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
(R9462)