Discharge Pressure Check - Daikin CTXU25G2V1B Service Manual

Inverter multi system with humidifying
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

Check

3.10 Discharge Pressure Check

Check No.16
175

Discharge pressure check

Is it high?
YES
Is the stop valve open?
YES
Is the connection pipe
deformed?
NO
Are the heat exchanger
and air filter dirty?
NO
NO
NO
YES
YES
SiBE12-908
Replace the compressor.
Open the stop valve.
Replace the field piping.
Clean it.
Replace the compressor.
(R9683)
Service Diagnosis