The errors indicated on the GHP
Wired Remote Controller
The error of outdoor unit, indoor unit and optional
accessories is indicated on the LCD.
If the
is indicated, press the
the wired remote controller to display the error code.
In case of displaying same error of several indoor units,
the front number is displayed first.
Display
Outdoor unit PCB
Remote
controller
code
Sub code
# is indicated according to the unit ADDRESS (0~F).
Explanation
Communication error
between the wired
#
remote controller and
indoor unit
The same ADDRESS
#
errors
Indoor and outdoor unit
0
connection error
Indoor and outdoor unit
0
communication error
Communication error
between the indoor unit
0
and centralized
controller
button in front of
Trouble
After communication between the wired
remote controller and indoor unit more than
once and communication cuts off for
2 minutes continuously
The same ADDRESS of the indoor unit
No outdoor unit which is correspond to the
indoor unit
- Communication error after communication
between wired remote controller and indoor
unit more than once
- Error is displayed from the indoor unit during
operation
- Communication error after communication
between wired remote controller and indoor
unit more than once
- Error detected from the outdoor unit
(60 seconds during operation,
150 seconds during off)
The self - transmission data is not received
After communication between wired remote
controller and centralized controller more than
once and cut off for 2 minutes continuously
Examination
frquency
(times
)
1
1
1
1
1
1
1
21