Summary of Contents for Samsung MWR-WE10N

  • Page 2: Air Conditioner

    Wired remote controller MWR-WE10N Air Conditioner installation manual This manual is made with 100% recycled paper. imagine the possibilities Thank you for purchasing this Samsung product. RU AR DB68-03716A(1)
  • Page 3: Safety Information

    Safety Information This installation manual explains how to install a Wired Remote Controller connected to the indoor unit of your Trane system air conditioner. Please read this manual thoroughly before installing the product. (Please refer to appropriate installation for any optional product installation.) WARNING Hazards or unsafe practices that may result in severe personal injury or death.
  • Page 4 CAUTION Do not install the product where there’s combustible gas. Potential risk of fire and explosion. Ensure no water gets into the Wired Remote Controller. Potential risk of electric shock or fire. Install the air conditioner away from direct exposure to sunlight, in room temperature range of 0°C(32°F)~39°C(102°F). Potential risk of electric shock or malfunction.
  • Page 5: Wired Remote Controller Installation

    Wired Remote Controller Installation Optional accessories Wired Remote Installation Cable Tie (2) Cable Clamp(3) M4X16 Screw (5) User Manual (1) U Terminal (4) Controller (1) Manual (1) • The Wired Remote Controller should be installed by an installation expert. • Check and confirm the power is off before installing your Wired Remote Controller. •...
  • Page 6 Wired Remote Controller Installation 1. Push the two hooks at the bottom of your Wired Remote Controller at the same time, and then pull up the front cover to separate it from the rear cover. Push the two hooks at the same time. •...
  • Page 7 Wired Remote Controller Installation Wired Remote Controller Installation 3. Using more than two screws, firmly affix the rear cover of the remote controller to the wall, and then connect the communication & power cable[(F3,F4) or (3, 4)], making sure these cables have reasonable length, to the terminal at the back of the cover.
  • Page 8 Tracking Your Indoor Unit from the Wired Remote Controller Indicates tracking in progress Displays the total number of units searched 1. Tracking of your Wired Remote Controller will automatically start when you turn on the power after installation. 2. If you want to perform tracking again after installation, then press the Esc and Delete buttons at the same time for more than five seconds.
  • Page 9 Wired Remote Controller Installation Individual Control with Your Wired Remote Controller Individual control means that you are using one remote controller to control one indoor unit or ventilator(ERV). When Connected to an Indoor Unit Only Outdoor Unit COM1(F1, F2) COM1(F1, F2) Indoor Unit Indoor Unit Indoor Unit...
  • Page 10 Group Control with Your Wired Remote Controller Group control means that you are using one Wired Remote Controller to control two or more indoor units and ventilator(ERV) at the same time. When Connected to an Indoor Unit Only (1) Using One Wired Remote Controller to control three indoor Units Outdoor Unit COM1(F1, F2) COM1(F1, F2)
  • Page 11 Wired Remote Controller Installation When Connected to an ventilator(ERV) Only (1) Using One Wired Remote Controller to Control Three ventilator(ERV) Master ventilator(ERV) COM1(F1, F2) COM1(F1, F2) COM1(F1, F2) Ventilator(ERV) Ventilator(ERV) Ventilator(ERV) COM2(F3, F4) COM2(F3, F4) Wired Remote Controller • Regardless of the ventilator(ERV)'s group address (RMC address), only the ventilator(ERV) connected to COM2 controlled in group.
  • Page 12 When Connected to an Indoor Unit and an ventilator(ERV) together (1) Using One Wired Remote Controller to control multiple indoor units and ventilator(ERV) Outdoor Unit COM1(F1, F2) COM1(F1, F2) COM1(F1, F2) Ventilator(ERV) Indoor Unit Indoor Unit Indoor Unit COM2(F3, F4) COM2(F3, F4) COM2(F3, F4) Wired Remote...
  • Page 13 Wired Remote Controller Installation Controlling 2-Remote controller 2-Remote controller is controlling one indoor unit, ventilator(ERV) or one group of indoor units and ventilator(ERV) with two remote controllers. When Connected to an Indoor Unit Only Outdoor Unit COM1(F1, F2) Indoor Unit COM2(F3, F4) Wired Remote Wired Remote...
  • Page 14 When Connected to an Indoor Unit and an ventilator(ERV) Together Outdoor Unit COM1(F1, F2) Indoor Unit COM2(F3, F4) COM2(F3, F4) Ventilator(ERV) Wired Remote Wired Remote Controller (Master) Controller (Slave) • Regardless of the indoor unit group address (RMC address), only the indoor units connected to COM2 are controlled by 2-remote controller.
  • Page 15 Wired Remote Controller Installation Initializing Your Wired Remote Controller Communication If the number of indoor unit or ventilator(ERV) is decreased while you are using your remote control to control one indoor unit, ventilator(ERV) or a group of indoor units and ventilator(ERV), then you need to initialize your remote controller communication.
  • Page 16 Errors Displayed on Your Wired Remote Controller Error codes for the Wired Remote Controller and the product connected to your Wired Remote Controller will be displayed in the LCD display. LCD Display When an Error Occurs in Your Indoor/Outdoor Units (Product Group Display: A) The product address for the error will be displayed, followed by the error code.
  • Page 17 Wired Remote Controller Installation Wired Remote Controller Error Codes Display Description Communication error between wired remote controller and indoor/ERV units after successful communication. No communication between Master(Main) and Slave(Sub) wired remote controllers. No communication between wired remote controller and indoor/ERV units Over 16 indoor/ERV indoor units installed.
  • Page 18: Wired Remote Controller Installation/Service Mode

    Wired Remote Controller Installation/Service Mode Additional Functions of Your Wired Remote Controller Data bit Main Menu Sub-menu 1 2 3...
  • Page 19 Wired Remote Controller Installation/Service Mode 1. If you want to use the various additional functions for your Wired Remote Controller, press the Set and Esc buttons at the same time for more than three seconds. You will enter the additional function settings, and the [main menu] will be displayed. 2.
  • Page 20 Additional Functions of Your Wired Remote Controller • ‘NONE’ will be displayed if the indoor unit does not support the function. In some cases, the setting may not possible or it may be not applied though it is set on the unit. •...
  • Page 21 Wired Remote Controller Installation/Service Mode Main Data Factory Function Description Unit menu menu setting Indoor unit room temperature 1,2,3 Room temperature °C Indoor unit EVA IN temperature 1,2,3 EVA IN temperature °C Indoor unit EVA OUT temperature 1,2,3 EVA OUT temperature °C Indoor unit EEV step 1,2,3...
  • Page 22 Main Data Factory Function Description Unit menu menu setting Indoor unit Master setting/ 123456 address Master setting/checking checking (F3F4 line Indoor unit master) ERV unit Master setting/ 123456 address checking Mode master indoor unit Mode master indoor unit 123456 address checking setting/checking (F1F2 line Indoor unit master) 3)*...
  • Page 23 Wired Remote Controller Installation/Service Mode The example of Wired Remote Controller option setting method 1. Press Set and ESC buttons at the same time for more than 3 seconds. (Main menu) will be displayed and then press the [ ]/[ ] button to select no.1. 2.
  • Page 24 Memo...