Mitsubishi Electric FR-F700PJ Instruction Manual page 220

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

(2)
Controllability through communication
Controllability through communication in each operation mode is shown below.
Monitoring and parameter read can be performed from any operation regardless of operation mode.
Operation
Condition
Location
(Pr. 551 Setting)
2
(PU connector)
Control by
RS-485
communication
from PU
connector
Other than the
above
Control circuit
external
terminals

As set in Pr. 338 Communication operation command source and Pr. 339 Communication speed command source (Refer to page 214)

At occurrence of RS-485 communication error, the inverter cannot be reset from the computer.

Enabled only when stopped by the PU. At a PU stop, PS is displayed on the operation panel. As set in Pr. 75 PU stop selection. (Refer to page 193)

Some parameters may be write-disabled according to the Pr. 77 Parameter write selection setting and operating status. (Refer to page 196)

Some parameters are write-enabled independently of the operation mode and command source presence/absence. When Pr. 77 = "2", write is enabled.
(Refer to the parameter list on page 64) Parameter clear is disabled.

Available with multi-speed setting and terminal 4-5 (valid when AU signal is ON).
(3)
Operation at error occurrence
Operation
Error Definition
Condition
(Pr. 551 setting)
Inverter
fault
2 (PU connector)
PU
9999 (automatic
disconnection of
recognition)
the PU
Other than the
above
RS-485
2 (PU connector)
communication
error of the PU
Other than the
connector
above

Can be selected using Pr. 75 Reset selection/disconnected PU detection/PU stop selection.

Can be selected using Pr. 122 PU communication check time interval.

In the PU JOG operation mode, operation is always stopped when the PU is disconnected. Whether fault (E.PUE) occurrence is allowed or not is as set in
Pr. 75 Reset selection/disconnected PU detection/PU stop selection.
Selection of operation mode and operation location
Operation
Mode
PU
Operation
Item
Run command (start)
Run command (stop)
Running frequency
setting

Parameter write
Inverter reset
Run command (start)
Run command (stop)
Running frequency
setting

Parameter write
Inverter reset
Inverter reset
Run command
(start, stop)
Frequency setting
Mode
External
PU Operation
Operation
Stop
Stop/continued 
Stop/continued
Stop/
Continued
continued
Continued
External/PU
External
Combined
Operation Mode 1
Operation
(Pr. 79 = 3)







: Enabled, : Disabled, : Some are enabled
External/PU
External/PU
Combined
Combined
Operation Mode
Operation Mode
1
2
(Pr. 79 = 3)
(Pr. 79 = 4)
Stop/continued —
External/PU
Combined
NET Operation
Operation Mode 2
(Pr. 79 = 4)










NET Operation
Stop/continued
4
215