Outdoor Fan Motor Control - Toshiba RAS-18, 22SKV-E Service Manual

Hide thumbs Also See for RAS-18, 22SKV-E:
Table of Contents

Advertisement

Item
3. Outdoor fan
The blowing air volume at the outdoor unit side is controlled.
motor control
Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed.
∗ For the fan motor, a DC motor with non-stage variable
speed system is used. However, it is limited to 8 stages for
reasons of controlling.
Air conditioner ON
(Remote controller)
Indoor unit controller
1) Outdoor unit
operation command
(Outdoor fan control)
2) Fan speed ≥ 400
when the motor stopped.
Fan motor ON
3) Fan lock
4) Motor operates as shown in the table below.
In cooling operation
Compressor speed (rps)
To > 38°C
To
> 28°C
To > 15°C
To
To > 5.5°C
To > 0°C
To
> -5°C
To > 38°C
To
> 28°C
During ECO,
To > 15°C
QUIET and
To > 5.5°C
comfort sleep
To > 0°C
To
> -5°C
When To is abnormal
18SAV-E2
Tap
18SAV2-E
18SAV2-A
f 0
0
f 1
230
f 2
300
f 3
350
f 4
410
f 5
480
f 6
500
f 7
530
Operation flow and applicable data, etc.
YES
fan motor continues.
NO
YES
Air conditioner
NO
< 22.1
< 50.3
MIN MAX MIN MAX MIN MAX
f 6
f 9
f 8
f B
f 5
f 9
f 7
f B
f 3
f 7
f 5
f 9
f 1
f 3
f 1
f 7
f 1
f 3
f 1
f 5
f 0
f 1
f 0
f 3
f 6
f 9
f 8
f B
f 5
f 9
f 7
f B
f 3
f 7
f 5
f 9
f 1
f 3
f 1
f 7
f 1
f 3
f 1
f 5
f 0
f 1
f 0
f 3
f 1
f F
f 1
f F
Outdoor fan speed (rpm)
22SAV-E2
22SAV2-E
Tap
22SAV2-A
0
f 8
230
f 9
300
f A
350
f B
410
f C
480
f D
500
f E
530
f F
OFF status of
Alarm
OFF
display
50.3 <
Compressor speed (rps)
f A
f E
To
f 9
f E
f 7
f B
f 3
f 9
f 3
f 7
During
f 1
f 4
ECO mode
f A
f B
f 9
f B
When To is abnormal
f 7
f B
f 3
f 9
f 3
f 7
f 1
f 4
f 1
f F
18SAV-E2
22SAV-E2
18SAV2-E
22SAV2-E
18SAV2-A
22SAV2-A
560
560
640
640
670
670
700
750
800
920
800
920
900
1000
900
1000
– 37 –
FILE NO. SVM-10050
Description
1) The operation command sent
from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the fan
motor stopped.
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
In Heating operation
< 30.5
< 55.1
To > 10°C
f 6
f 8
To > 5.5°C
f 8
f A
To > -5°C
f A
f B
To
-5°C
f A
f B
To > 10°C
f 5
f 7
To > 5.5°C
f 7
f 9
To > -5°C
f 9
f A
To
-5°C
f 9
f A
f D
f D
55.1 <
f 9
f C
f D
f D
f 9
f B
f B
f B
f D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents