Installation sequence
Power supply
■ The heat pump control unit/PCB
must be supplied without power-OFF;
tariffs that are subject to possible shut-
down must not be used here
■ Protect the power supply to the heat
pump control unit with max. 16 A
■ For accessories and external compo-
nents that are not to be connected to
the heat pump control unit, connect the
power supply with the same phase as
the heat pump control unit; we recom-
mend using the same fuse/MCB.
Connection to the same fuse/MCB
provides additional safety when the
power is switched off. Observe the
power consumption of the connected
consumers

Heat pump control unit power supply (230 V~)

X3
6
7
8
9
16
16
18
F1 T6,3AH
L1
N
60
(cont.)
X2
X1
N
N
3
1
1
Note
This supply must never be blocked.
■ Max. fuse rating 16 A
■ Standard tariff (no optional economy
tariff with power-OFF)
■ Recommended power cable:
2
3 x 1.5 mm
(5 x 1.5 mm
off by the power supply utility)
2
with power-