Type AWT-AC
Air intake temperature
Cooling mode
■ Min.
■ Max.
Heating mode
■ Min.
■ Max.
Heating water
at 10 K spread
Capacity
Minimum flow rate
(always maintain)
Max. external pressure
drop (RFH) at min. flow
rate
Max. flow temperature
Electrical values
External unit
■ Rated voltage, com-
pressor
■ Max. rated current,
compressor
■ Starting current,
compressor
■ Compressor starting
current with stalled
armature
■ Starting current
(charging DC capaci-
tors)
■ Internal fuse/MCB
■ IP rating
221.A04
°C
15
°C
45
°C
–15
°C
35
l
16.7
l/h
600
mbar
590
°C
55
A
5
A
10.5
A
20
A
45
A
3.5
IP
24
221.A07
221.A10
15
15
45
45
–15
–15
35
35
16.7
17.7
820
1200
540
440
55
55
1/N/PE 230 V/50 Hz
9
10
15
10
25
25
< 35
30
3.5
3.15
24
24
Specification
221.A13
15
45
–15
35
17.7
1380
380
55
15
10
32
30
3.15
24
127