20.8 - Refrigerant volume

The unit must be operated in cooling mode to find out, if
the unit charge is correct, by checking the actual subcooling.
Following a small refrigerant leak a loss of refrigerant,
compared to the initial charge will be noticeable in the
cooling mode and affect the subcooling value obtained at
the air heat exchanger (condenser) outlet, but it will not be
noticeable in the heating mode.
ImpOrTANT: It is therefore not possible to optimise the
refrigerant charge in the heating mode after a leak. The
unit must be operated in the cooling mode to check, if an
additional charge is required.

20.9 - Characteristics of R-410a

Saturated temperatures (°C) based on the relative pressure (in kpa)
Saturat.
Relative
Saturat.
Relative
temp.
pressure
temp.
pressure
-20
297
4
807
-19
312
5
835
-18
328
6
864
-17
345
7
894
-16
361
8
924
-15
379
9
956
-14
397
10
987
-13
415
11
1020
-12
434
12
1053
-11
453
13
1087
-10
473
14
1121
-9
493
15
1156
-8
514
16
1192
-7
535
17
1229
-6
557
18
1267
-5
579
19
1305
602
1344
-4
20
-3
626
21
1384
-2
650
22
1425
-1
674
23
1467
0
700
24
1509
1
726
26
1596
2
752
25
1552
3
779
27
1641
Aquasnap units use high-pressure R-410A refrigerant (the
unit operating pressure is above 40 bar, the pressure at 35°C
air temperature is 50% higher than for R-22). Special
equipment must be used when working on the refrigerant
circuit (pressure gauge, charge transfer, etc.).
46
Saturat.
Relative
Saturat.
Relative
temp.
pressure
temp.
pressure
28
1687
52
3088
29
1734
53
3161
30
1781
54
3234
31
1830
55
3310
32
1880
56
3386
33
1930
57
3464
34
1981
58
3543
35
2034
59
3624
36
2087
60
3706
37
2142
61
3789
38
2197
62
3874
39
2253
63
3961
40
2311
64
4049
41
2369
65
4138
42
2429
66
4229
43
2490
67
4322
2551
4416
44
68
45
2614
69
4512
46
2678
70
4610
47
2744
48
2810
49
2878
50
2947
51
3017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: