Application Data; Operating Range, Standard Units - Cooling Mode; Operating Range, Standard Units - Heating Mode - Carrier 30RQ 039 Series Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pumps
Table of Contents

Advertisement

Electrical data and operating conditions notes:
30RQS/RQSY 039-160 units have a single power connection point located
immediately upstream of the main disconnect switch.
The control box includes the following standard features:
-
a main disconnect switch,
-
starter and motor protection devices for each compressor, the fans and
the pump,
-
the control devices.
field connections:
All connections to the system and the electrical installations must be in full
accordance with all applicable local codes.
The Carrier 30RQS/RQSY units are designed and built to ensure conformance
with these codes. The recommendations of European standard EN 60204-1
(machine safety - electrical machine components - part 1: general regulations -
corresponds to IEC 60204-1) are specifically taken into account, when
designing the electrical equipment.
NOTES:
Generally the recommendations of IEC 60364 are accepted as compliance with
the requirements of the installation directives. Conformance with EN 60204-1
is the best means of ensuring compliance with the Machines Directive § 1.5.1.
Annex B of EN 60204-1 describes the electrical characteristics used for the
operation of the machines.
The operating environment for the 30RQS/RQSY units is specified below:
1. Environment* - Environment as classified in EN 60721 (corresponds to IEC
60721):
-
outdoor installation*
-
ambient temperature range: -20°C to +48°C, class 4K4H

10 - applICaTION DaTa

10.1 - Operating range, standard units - cooling mode

Evaporator
Entering water temperature at start-up
Leaving water temperature during operation
Entering/leaving water temperature difference
Condenser
Entering air temperature 30RQS***
Entering air temperature 30RQSY***
Hydronic module****
Entering air temperature
Kit without pump
Kit with pump (option 116x)
Kit with pump (option 116x) and frost protection
option to -20°C (option 42)
Note: Do not exceed the maximum operating temperature.
*
For entering water temperatures below 7.5°C at start-up, contact Carrier.
**
For low-temperature applications, where the leaving water temperature is
below 5°C, a frost protection solution must be used.
*** For transport and storage of the 30RQS/30RQSY units the minimum and
maximum allowable temperatures are -20°C and +48°C. It is recommended that
these temperatures are used for transport by container.
**** Defines the frost-free temperature of the hydronic components for use without
glycol.
30RQS/RQSY - cooling mode
50
40
30
20
10
0
-10
-20
0
5
10
Evaporator leaving water temperature, °C
NOTE: This operating range applies up top 130 pa static
pressure without suction air duct for sizes 060, 070 and
078 and 140-160, and up to 240 pa for all other sizes.
24
Minimum
Maximum
°C
7.5*
30
°C
5**
20
K
3
10
Minimum
Maximum
°C
-10
48
°C
-20
48
°C
-20
-
°C
0
-
°C
-20
-
30RQS
Full load
30RQSY
Minimum load
15
20
25
-
altitude: ≤ 2000 m (see note for table 9.2 - Electrical data, hydronic module)
-
presence of hard solids, class 4S2 (no significant dust present)
-
presence of corrosive and polluting substances, class 4C2 (negligible)
2. Power supply frequency variation: ± 2 Hz.
3. The neutral (N) conductor must not be connected directly to the unit (if
necessary use a transformer).
4. Overcurrent protection of the power supply conductors is not provided with the
unit.
5. The factory-installed disconnect switch is of a type suitable for power
interruption in accordance with EN 60947.
6. The units are designed for simplified connection on TN(s) networks (IEC 60364).
For IT networks provide a local earth and consult competent local organisations
to complete the electrical installation. Units delivered with speed drive
(options 28 and 116J/K/V/W) are not compatible with IT network.
7. Derived currents: If protection by monitoring of derived currents is necessary to
ensure the safety of the installation, the control of the cut-out value must take the
presence of leak currents into consideration that result from the use of frequency
converters in the unit. A value of at least 150 mA is recommended to control
differential protection devices.
Caution: If particular aspects of an actual installation do not conform to the
conditions described above, or if there are other conditions which should
be considered, always contact your local Carrier representative.
*
The required protection level for this class is IP43BW (according to reference
document IEC 60529). All 30RQS/RQSY units are protected to IP44CW and
fulfil this protection condition.

10.2 - Operating range, standard units - heating mode

Condenser
Entering water temperature at start-up
Leaving water temperature during operation
Entering/leaving water temperature difference
Evaporator
Air temperature
Hydronic module*
Entering air temperature
Kit without pump
Kit with pump (option 116x)
Kit with pump (option 116x) and frost protection
option to -20°C (option 42)
Note: Do not exceed the maximum operating temperature.
*
Defines the frost-free temperature of the hydronic components for use without
glycol.
30RQS/RQSY - heating mode
60
55
50
45
40
35
30
25
20
-20
-10
0
10
Entering air temperature, °C
Minimum
Maximum
°C
8
45
°C
25
55
K
3
10
Minimum
Maximum
°C
-15
40
°C
-20
-
°C
0
-
°C
-20
-
Full load
Minimum load
20
30
40
50