G71Mpp−60C−090 Blower Performance (Less Filter) - Lennox G71MPP SERIES Unit Information

Hide thumbs Also See for G71MPP SERIES:
Table of Contents

Advertisement

Bottom Return Air, Return Air from Both Sides or Return Air from Bottom and One Side
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
Increase (+15%) Heat CFM
Increase (+7.5%) Heat CFM
Default Heat CFM
Decrease (–7.5% ) Heat CFM
Decrease (–15% ) Heat CFM
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
Increase (+10%) Cool CFM
Default Cool CFM
Decrease (–10%) Cool CFM
The effect of static pressure is included in air volumes shown.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 450 cfm.
The following control board configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Mode (Heating Blower Performance Table):
With a single−stage thermostat, furnace will operate at three, staged rates (40/70/100%) with a time delay between each stage (values in grey−shaded
columns).
With two−stage thermostat there are two modes available.
Traditional two−stage mode − W1 demand results in 70% firing rate. W2 results in 100% firing rate. No delay between stages. (values shown in 70%
and 100% grey−shaded columns only).
Variable Rate Capacity Mode − furnace automatically adjusts firing rate based on first− and second−stage cycle times. (all columns)
Cool Mode (Cooling Blower Performance table):
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second−stage COOL speed position
minimum 450 cfm.
G71MPP−60C−090 BLOWER MOTOR WATTS − COOLING
Bottom Return Air, Return Air from Both Sides or Return Air from Bottom and One Side
Blower Speed
Options
0
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80
Increase (+10%) Cool CFM
Low
115
135
Medium−Low 145
165
Medium−High 170
200
High
265
295
Default Cool CFM
Low
90
110
Medium−Low
110
130
Medium−High 145
165
High
180
205
Decrease (–10%) Cool CFM
Low
70
85
Medium−Low
80
100
Medium−High
110
130
High
155
175
G71MPP−60C−090 BLOWER PERFORMANCE (less filter)
0 through 0.80 in. w.g. External Static Pressure Range
40%
665
600
615
520
465
First Stage Cool Speed − cfm
Medium−
Medium
Low
Low
1105
1185
995
1080
890
960
Motor Watts @ Various External Static Pressures − in. wg.
First Stage
160
185
205
230
255
190
215
240
265
285
240
275
305
335
370
330
365
400
435
465
130
155
175
195
215
155
180
200
220
245
190
215
245
270
295
240
270
300
330
365
105
125
145
165
185
120
140
165
190
210
160
185
205
225
250
195
220
245
270
295
TABLE 3
Heating Input Range and Blower Volume − CFM
50%
60%
70%
800
935
1070
730
860
990
715
820
920
630
740
850
565
665
765
Blower Speed Selections
High
Low
High
(Default)
1355
1545
1605
1205
1345
1440
1090
1215
1275
0
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80
275
300
305
340
305
325
355
390
400
430
510
555
500
535
725
780
235
255
220
250
265
285
270
305
320
340
390
425
395
430
540
580
205
225
160
190
225
245
195
225
275
300
295
330
315
340
400
435
Page 6
80%
90%
1205
1335
1110
1235
1035
1150
960
1070
870
970
Second Stage Cool Speed − cfm
Medium−
Medium
Low
High
1710
1925
1560
1755
1380
1590
Second Stage
375
410
440
475
505
430
470
510
550
580
600
645
690
730
765
835
895
935
975 1005 1035 1065
285
320
350
385
415
345
385
420
455
485
465
500
540
580
610
625
670
710
755
795
220
255
275
300
330
260
295
325
350
385
365
400
430
460
495
470
510
545
585
610
100%
1470
1355
1265
1180
1075
High
(Default)
2165
1960
1755
535
565
610
635
795
830
450
485
515
545
640
670
830
870
360
390
415
450
535
570
640
665