TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
PLUG
VENT PLUG
(Must be
glued in
place)
PLUG
*2" diameter street elbow provided.
**3" to 2" diameter reducing elbow provided.
*** Max 2" pipe length between reducing
elbow and transition when 4" pipe is used.
TYPICAL EXHAUST PIPE CONNECTIONS
HORIZONTAL DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
*2" maximum length
for −135 only.
DO NOT transition from
smaller to larger pipe
size in horizontal runs.
FIGURE 20
IN UPFLOW OR DOWNFLOW DIRECT VENT APPLICATIONS
(Right−Hand Exit in Upflow Application Shown)
2"
PLUG
or
2"
2"
2"
CONDENSATE
TRAP
TRANSITION
(Must be installed
on same side as
exhaust piping)
FIGURE 19
−36B−070
2−1/2",
−36C−090
3", OR
−60C−090
4"
−60C−110*
−60D−135*
TRANSITION
2" dia.
pipe*
2"
2"
−36B−070
−36C−090
2"
−60C−090
2−1/2",
3", OR
4"
TRANSITION
2"
G71MPP−070,
or −090 with
2−1/2", 3", or 4"
2"
vent pipe
2−1/2",
3", OR
4"
TRANSITION
(use only if 4"
pipe is
required)
2" dia. pipe
2"*
G71MPP−110 with
2−1/2", 3", OR 4"
vent pipe

Intake Piping

The G71MPP furnace may be installed only in direct vent
applications.
The G71MPP unit is designed for either left−side or right−
side air intake connections in either upflow or downflow ap-
plications. In horizontal applications, air intake must be
brought in through the top. Intake air piping is independent
of exhaust piping.
Page 40
45°
45°
MAX
MAX
SIDE VIEW
4"
3" dia. pipe***
2"**
G71MPP−135 with
3" OR 4" vent pipe