Trane UniTrane Installation, Operation And Maintenance Instructions page 8

Fan-coil and air conditioners
Table of Contents

Advertisement

Model Number Descriptions
Digits 21, 22, 23 — Electric Heat
kW — ( ) = 208 V Derate
000 =
No Electric Heat
010 =
1.0 kW (0.75 kW)
015 =
1.5 kW (1.1 kW)
020 =
2.0 kW (1.5 kW)
025 =
2.5 kW (1.9 kW)
030 =
3.0 kW (2.3 kW)
040 =
4.0 kW (3.0 kW)
050 =
5.0 kW (3.8 kW)
060 =
6.0 kW (4.5 kW)
070 =
7.0 kW (5.3 kW)
080 =
8.0 kW (6.0 kW)
100 =
10.0 kW
Digit 24 — Reheat Coil
0
=
None
A
=
Steam Coil
B
=
Hot Water Coil
D
=
High Capacity Hot Water Coil
Digit 25 — Disconnect Switch
0
=
None
D
=
Disconnect Switch
Digit 26 — Filter
0
=
None
1
=
1" Throwaway Filter
2
=
1" Throwaway MERV 8 Filter
3
=
1" Throwaway, 1 Extra
4
=
1" Throwaway MERV 8, 1 Extra
5
=
1" Throwaway, 2 Extras
6
=
1" Throwaway MERV 8, 2 Extras
7
=
1" Throwaway, 3 Extras
8
=
1" Throwaway MERV 8, 3 Extras
8
Digit 27 — Main Control Valve
0
=
None
A
=
2-Way, 2-Position, NO (30 psig)
B
=
3-Way, 2-Position, NO (28 psig)
C
=
2-Way, 2-Position, NC (30 psig)
D
=
3-Way, 2-Position, NC (20 psig)
E
=
2-Way, 2-Position, NO (50 psig)
F
=
3-Way, 2-Position, NO (28 psig)
G
=
2-Way, 2-Position, NC (50 psig)
H
=
3-Way, 2-Position, NC (28 psig)
J
=
2-Way, Modulating, 0.6 Cv
(60 psig)
K
=
3-Way, Modulating, 0.6 Cv
(60 psig)
L
=
2-Way, Modulating, 1.1 Cv
(60 psig)
M =
3-Way, Modulating, 1.1 Cv
(60 psig)
N
=
2-Way, Modulating, 2.3 Cv
(60 psig)
P
=
3-Way, Modulating, 2.7 Cv
(60 psig)
Q
=
2-Way, Modulating, 3.3Cv
(60 psig)
R
=
3-Way, Modulating, 3.8 Cv
(60 psig)
X
=
Field-supplied, NO
Y
=
Field-supplied, NC
Z
=
Field-supplied 3-Wire Modulating
Digit 28 — Auxiliary Control
Valve
0
=
None
A
=
2-Way, 2-Position, NO (30 psig)
B
=
3-Way, 2-Position, NC (28 psig)
C
=
2-Way, 2-Position, NC (30 psig)
D
=
3-Way, 2-Position, NC (20 psig)
E
=
2-Way, 2-Position, NO (50 psig)
F
=
3-Way, 2-Position, NO (28 psig)
G
=
2-Way, 2-Position, NC (50 psig)
H
=
3-Way, 2-Position, NC (28 psig)
J
=
2-Way, Modulating, 0.6 Cv
(60 psig)
K
=
3-Way, Modulating, 0.6 Cv
(60 psig)
L
=
2-Way, Modulating, 1.1 Cv
(60 psig)
M =
3-Way, Modulating, 1.1 Cv
(60 psig)
N
=
2-Way, Modulating, 2.3 Cv
(60 psig)
P
=
3-Way, Modulating, 2.7 Cv
(60 psig)
Q
=
2-Way, Modulating, 3.3Cv
(60 psig)
R
=
3-Way, Modulating, 3.8 Cv
(60 psig)
X
=
Field-supplied, NO
Y
=
Field-supplied, NC
Z
=
Field-supplied 3-Wire Modulating
Digit 29 — Piping Packages
0
=
None
A
=
Basic Ball Valve Supply and
Return
B
=
Basic Ball Valve Supply/Manual
Circuit Setter
C
=
Basic Ball Valve Supply and
Return with Auto Circuit Setter
D
=
Deluxe Ball Valve Supply and
Return
E
=
Deluxe Ball Valve Supply/Manual
Circuit Setter
F
=
Deluxe Ball Valve Supply and
Return with Auto Circuit Setter
Digit 30 — Control Type
A
=
Fan Mode Switch
E
=
Tracer ZN010
F
=
Tracer ZN510
G
=
Tracer ZN520
H
=
Customer Supplied Thermostat
Interface (CSTI)
Digit 31 — Control Option
D
=
Unit-Mounted Fan Mode Switch
K
=
Wall-Mounted Fan Mode Switch
V
=
Unit-Mounted Fan Speed Switch
w/Setpoint Dial Zone Sensor
W =
Wall-Mounted Fan Speed Switch
w/Setpoint Dial Zone Sensor
X
=
Unit-Mounted Fan Speed Switch
w/Wall-Mounted Setpoint Dial
Zone Sensor
Y
=
Unit-Mounted Fan Speed Switch
& Wall-Mounted Setpoint Dial
w/Comm.
Z
=
Unit-Mounted Fan Speed Switch,
On/Cancel, Setpoint Dial
w/ Comm.
1
=
Wall-Mounted On/Cancel
w/ Comm.
2
=
Wall-Mounted Fan Speed Switch,
Setpoint Dial, On/Cancel
w/ Comm.
0
=
Without Control Option
3
=
Unit-Mounted Low Voltage Fan
Speed Switch (Off /Hi /Med /Low)
4
=
Wall-Mounted Digital Zone
Sensor (OALMH, Setpoint,
On/Cancel, Comm Jack)
5
=
Wall-Mounted Digital Zone
Sensor (On/Cancel, Comm Jack)
6
=
Wireless Zone Sensor
7
=
Wireless Display Sensor, Unit-
Mounted Receiver
Digit 32 - IAQ Options
0
=
Without IAQ Options
1
=
Dehumidification
4
=
Dehumidification w/ Sensor
Digits 33, 34 —Future Control
Functions
Digit 35 — Control Function #3
0
=
None
2
=
Condensate Overflow Detection
UNT-SVX07B-EN