Trane UniTrane Installation, Operation And Maintenance Instructions page 123

Fan-coil and air conditioners
Table of Contents

Advertisement

Table 45. Receiver resistance table for all models
Zone or setpoint temperature
55°F (12.8°C)
60°F (15.6°C)
65°F (18.3°C)
70°F (21.1°C)
75°F (23.9°C)
80°F (26.7°C
85°F (29.4°C)
Table 46. Receiver resistance table for model WDS
Fan command
High
Med
Low
Auto
Off
Cleaning the Sensor
NOTICE
Equipment damage!
Spraying glass cleaner or any other solution directly on the sensor may damage it.
You can clean the sensor by applying glass cleaner to a soft, non-abrasive cloth, and gently wiping
the face, including the buttons and LCD display. Use of a pre-moistened towelette designed for lens
or screen cleaning is also acceptable.
Avoid inadvertent pressing of the Occupied/Unoccupied buttons on the keypad on the WDS sensor
as this may result in an unwanted timed override or settings change.
UNT-SVX07B-EN
a. All models: Measure between the grounded GND-SIGNAL (black) wire and either the
SETPOINT (red) or ZONE (white) wire. Compare resistance measurements to those in
Table
45.
b. WDS only: Measure between the grounded GND-SIGNAL (black) wire and the FAN/SYSTEM
(green) wire. Compare resistance measurements to those given in
Note: The output circuits are not electrically powered; consequently, resistance can be
measured without risk of damage to the volt-ohm meter.
Nominal zone temperature
output resistance
17.47 kΩ
15.3 kΩ
13.49 kΩ
11.9 kΩ
10.5 kΩ
9.3 kΩ
8.25 kΩ
Nominal output resistance
16,130 Ω
13,320 Ω
10,770 Ω
2320 Ω
4870 Ω
Diagnostics
Table
46.
Nominal setpoint and heating
setpoint output resistance
792 Ω
695 Ω
597 Ω
500 Ω
403 Ω
305 Ω
208 Ω
123