Replacing the Sensor Cover

To replace the cover:
1. Hook the cover over the top of the back plate. Apply light pressure to the bottom of the cover
2. Install the security screw into the bottom of the cover (if desired).

Sensor Operations

Temporary Occupancy (Timed Override)
Temporary occupancy (timed override) is available on model WDS. Temporary occupancy is
selected for after-business-hours adjustment of temperature setting, fan settings, or heat/cool
settings, when the system has changed to unoccupied mode. System control will revert to
unoccupied after a pre-determined time period.
Note: Not all systems support the occupancy function.
Model WDS Sensor
To request and cancel temporary occupancy on a model WDS sensor, see
Occupancy, " p.
End-of-Range Temperature Values
Receiver: The end-of-range temperature limits of the receiver for all models are 32°F to 122°F (0°C
to 50°C). The receiver cannot replicate temperature values outside this range. If the sensor
transmits a temperature value to the receiver that is out of the receiver replication range, the
receiver will "freeze" the output at the end-of-range values. This value will remain frozen until the
transmitted temperature moves to between the end-of-range temperature limits.
Sensor: The end-of-range temperature setpoint limits for the model WDS sensor is 50°F (10°C) to
89.6°F (32°C).
UNT-SVX07B-EN
If you press a keypad button to try change a locked setting, the locked symbol will flash.
until it snaps in place.
78.
Security screw
Controls Interface
will appear on the display.
"Requesting Temporary
75