Function
Heating circuit 1
Off | On
Heating circuit 2
Off | On
Heating circuit 3
Off | On
DHW sensor
DHW sensor B3 | Thermostat
DHW controlling element Q3
No charging request | Charging pump | Diverting valve
Basic pos DHW div
Last request | Heating circuit | DHW
DHW separate circuit
Off | On
Contact type DHW div valve
Position on DHW | Position on HC
Ctrl boiler pump/DHW valve
All requests | Request HC1/DHW only
Solar controlling element
Charging pump | Diverting valve
External solar exchanger
Commonly | DHW storage tank | Buffer storage tank
Combi storage tank
No | Yes
Relay output QX1
None | Circulating pump Q4 | El imm heater DHW K6 | Collector pump
Q5 | Cons circuit pump VK1 Q15 | Boiler pump Q1 | Alarm output K10 |
Heat circuit pump HC3 Q20 | Cons circuit pump VK2 Q18 | System
pump Q14 | Heat gen shutoff valve Y4 | Solid fuel boiler pump Q10 |
Time program 5 K13 | Buffer return valve Y15 | Solar pump ext exch
K9 | Solar ctrl elem buffer K8 | Solar ctrl elem swi pool K18 | Swim-
ming pool pump Q19 | Cascade pump Q25 | St tank transfer pump
Q11 | DHW mixing pump Q35 | DHW interm circ pump Q33 | Heat re-
quest K27 | Heat circuit pump HC1 Q2 | Heat circuit pump HC2 Q6 |
DHW ctrl elem Q3 | Status output K35 | Status information K36 | Flue
gas damper K37 | Fan shutdown K38
Relay output QX2
Parameters see Relay output QX1 (prog.-no. 5890)!
Relay output QX3
Parameters see Relay output QX1 (prog.-no. 5890)!
Sensor input BX1
None | DHW sensor B31 | Collector sensor B6 | DHW circulation sensor
B39 | Buffer sensor B4 | Buffer sensor B41 | Common flow sensor B10 |
Solid fuel boiler sensor B22 | DHW charging sensor B36 | Buffer sensor
B42 | Common return sensor B73 | Cascade return sensor B70 | Swim-
ming pool sensor B13 | Solar flow sensor B63 | Solar return sensor B64
Sensor input BX2
Parameters see Sensor input BX1 (prog.-no. 5930)!
Sensor input BX3
Parameters see Sensor input BX1 (prog.-no. 5930)!
7308272-03 03.14
Prog.
5710
5715
5721
5730
5731
5734
5736
5737
5774
5840
5841
5870
5890
5891
5892
5930
5931
5932
Paramount three 30-115 kW
Programming
Standard value
1)
Level
no.
C
On
C
Off
C
Off
E
DHW sensor B3
E
Charging pump
E
Heating circuit
E
Off
E
Position on DHW
E
All requests
E
Charging pump
E
Commonly
E
No
C
None
C
Heat circuit pump HC1
Q2
C
DHW controlling element
Q3
C
Collector sensor B6
C
DHW sensor B31
C
Buffer st tank sensor B4
65