Potterton Paramount three 30 Installation Manual page 105

Hide thumbs Also See for Paramount three 30:
Table of Contents

Advertisement

With solar integration
(5093)
Pump speed limitations
(5101, 5102)
Speed Xp
(5103)
Speed Tn
(5104)
Speed Tv
(5105)
Transfer strategy
(5130)
Interm circ boost recharging
(5139)
Intermediate circuit boost
(5140)
Excess interm circ temp max
(5141)
Flow setp compensation de-
lay
(5142)
Flow setp compensation Xp
(5143)
Flow setp compensation Tn
(5144)
Flow setp compensation Tv
(5145)
Full charging with B36
(5146)
7308272-03 03.14
This function sets whether the DHW storage tank should be filled.
Setting of the minimum and maximum speed of the storage tank charging pump
in percent.
The P-band Xp defines the amplification of the controller A smaller Xp value leads
to a higher actuation of the charging pump with equal control difference.
The reset time Tn determines the reaction speed of the controller when compen-
sating for remaining controller differences. A shorter reset time Tn leads to faster
compensating.
The preholding time Tv determines how long a spontaneous change of the con-
trol difference continues to have an effect. A short time only influences the con-
trol variable only for a short time.
The transfer is always allowed or to the set DHW release times.
Setpoint boost for charging setpoint on charging sensor B36 with recharging.
Setpoint boost for charging setpoint on charging sensor B36 with full charging.
With this parameter the end criterion of a full charging during control is specified
on the charging sensor B36. If the contents of the layer storage is charge to the
bottom, the temperature increases on the charging sensor
The filter time for the setpoint lead is set here.
The P-band Xp defines the amplification of the controller A smaller Xp value leads
to higher actuation of the charging pump with equal control difference.
The reset time Tn determines the reaction speed of the controller when compen-
sating for remaining controller differences. A shorter reset time Tn leads to faster
compensating.
The preholding time Tv determines how long a spontaneous change of the con-
trol difference continues to have an effect. A short time only influences the con-
trol variable only for a short time.
Here it can be set whether the end of the full charging is detected via the temper-
ature on the charging sensor B36.
- No: the end of the full charging is detected via the temperature on the upper
and lower storage sensor B3 and B31.
- Yes: the end of the full charging is detected via the temperature on the upper
storage sensor B3.
Paramount three 30-115 kW
Programming
105