Potterton Paramount three 30 Installation Manual page 112

Hide thumbs Also See for Paramount three 30:
Table of Contents

Advertisement

Programming
Central setp compensation
(6117)
Frost protection plant
(6120)
Saving sensors
(6200)
Reset to default parameters
(6205)
Control numbers generator
1/storage/heating circuit
(6212, 6213, 6215, 6217)
Tab. 11: Check no. heat source 1 (prog.-no. 6212)
0
1
3
5
6
8
9
10
11
112
The central setpoint lead monitors the heat generator setpoint to the required
central flow temperature. With the setting the maximum corrector is restricted,
even if a large adaptation is required.
The heating circuit pump will be activated by the outside temperature without
heat request If the outside temperature reaches the lower setpoint of -4°C,the
heating circuit pump will be activated. If the outside temperature is between -5°C
and +1.5°C, the pump will be activated every 6 hours for 10 minutes. When reach-
ing the upper limit of 1.5°C, the pump will be switched off.
Sensor statuses can be stored under programme number 6200. This happens au-
tomatically; however, after changing the plant (removal of a sensor) the state at
the sensor terminals must be stored new.
The factory settings of the control unit will be written to the control unit.
Caution! The control parameters will be overwritten. The factory settings are stor-
ed in the control unit.
- Activation of the prog. no. 6205:
The control will be reset to the factory settings.
The basic device generates a control number for identification of the plant
scheme, which is composed of the numbers listed in Tab. 11 (Page 112)
Solar
X
X
X
X
X
X
Paramount three 30-115 kW
No solar
*
DHW/B
DHW+B
DHW/B
DHW
DHW
7308272-03 03.14