Potterton Paramount three 30 Installation Manual page 104

Hide thumbs Also See for Paramount three 30:
Table of Contents

Advertisement

Programming
Recooling temp
(5055)
Recooling collector
(5057)
El imm heater optg mode
(5060)
El immersion heater release
(5061)
El inmmersion heater control
(5062)
Automatic-Push
(5070)
Excess heat draw
(5085)
With buffer storage tank
(5090)
With primary control/system
pump
(5092)
104
Setting the temperature for recooling the DHW-storage.
Recooling of the overheated collector through giving off of the energie to the sur-
rounding of the collector.
- Replacement: the DHW is only heated by electrical immersion heater if the boil-
er signals a malfunction or a boiler lock exists.
- Summer: the DHW is heated by an electrical immersion heater if all connecting
heating circuits have switched to summer mode. As soon at least one heating
circuit is switched to heating mode, the DHW preparation is again taken over
by the boiler. The conditions listed for the electrical immersion heater under Re-
placement operating mode is also activated in the Summer operating mode.
- Always: the DHW preparation is only performed by the electrical immersion
heater.
- 24h/day: Permanent release of the electric insert
- DHW release: Release of the electric insert depending on DHW-release (see
prog.no. 1620).
- Time program 4/DHW: Release of the electric insert via the time switching pro-
gramme 4 of the local controller.
- External thermostat: The storage temperature will be achieved with an external
thermostat without setpoint control of the controller.
- DHW sensor: The storage temperature will be achieved with an external ther-
mostat with setpoint control of the controller.
The DHW-Push can activated by hand or automatically. It causes a one-time DHW
charging to the nominal setpoint.
- Off: The DHW-Push can only activated by hand.
- On: If the DHW temperature drops by more than two switching differences
(prog. no. 5024) below the reduced setpoint (prog. no. 1612), one -time it will
be recharged to the DHW nominal setpoint (prog.no.1610).
The automatic push only works for set DHW operating mode.
An excess heat draw can be actuated through the following functions: storage
tank temperature maximum, automatic push, charging priority time push, excess
heat draw, active inputs H1, H2, H3 or EX2, storage tank recooling, solid boiler ex-
cess heat draw. If an excess temperature discharge is activated, the excess energy
can be discharged through a heat draw of the room heating. This can be separate-
ly set for each heating circuit.
- No: The domestic hot water storage tank will be directly charged from the boil-
er.
- Yes: The domestic hot water storage tank will be charged from the buffer stor-
age tank.
- No: the domestic hot water storage tank will be charged without primary con-
troller/system pump.
- Yes: the domestic hot water storage tank will be charged from the primary con-
troller on/with the system pump.
Paramount three 30-115 kW
7308272-03 03.14