Programming
Function
Type of charging
Recharging | Full charging | Full charging legio | Full charg 1st. time
day | Full charg 1st time legio. charging
Switching diff
Charging time limitation
Discharging protection
Off | Always | Automatically
Charging temp max
Recooling temperature
Recooling collector
Off | Summer | Always
El imm heater optg mode
Substitute | Summer | Always
Electrical immersion heater release
24h/day | DHW release | Time program 4/DHW
El immersion heater control
External thermostat | DHW sensor
Automatic-Push
Off | On
Excess heat draw
Off | On
With buffer storage tank
No | Yes
With prim contr/system pump
No | Yes
With solar integration
No | Yes
Pump speed min
Pump speed max
Speed Xp
Speed Tn
Speed Tv
Transfer strategy
Always | DHW release
Interm circ boost recharging
Intermediate circuit boost
Excess interm circ temp max
Flow setp compensation delay
Flow setp compensation Xp
Flow setp compensation Tn
Flow setp compensation Tv
Full charging with B36
No | Yes
Min start temp diff Q33
Excess interm circ temp del
Configuration
64
Prog.
5022
5024
5030
5040
5050
5055
5057
5060
5061
5062
5070
5085
5090
5092
5093
5101
5102
5103
5104
5105
5130
5139
5140
5141
5142
5143
5144
5145
5146
5148
5151
Paramount three 30-115 kW
Standard value
1)
Level
no.
E
Full charging
E
4°C
E
120 min
E
Automatic
E
69°C
E
80°C
E
Off
E
Substitute
E
DHW release
E
DHW sensor
E
On
E
On
E
yes
E
yes
E
yes
E
0%
E
100%
E
35°C
E
120 s
E
45 s
E
Always
E
5°C
E
2°C
E
2°C
E
30 s
E
60°C
E
30 s
E
30 s
E
no
E
-3°C
E
30 s