Rigging Unit For Lifting; Horizontal Air Discharge; Condensate Drains; Units Equipped With An Optional Economizer - Lennox KGB024 Installation Instructions Manual

Gas and cooling packaged units
Table of Contents

Advertisement

Rigging Unit For Lifting

Rig unit for lifting by attaching four cables to holes in unit
base rail. See figure 2.
RIGGING
UNIT
KG
KC
*Maximum weight with all avail­
able installed accessories.
LIFTING POINT SHOULD
BE DIRECTLY ABOVE
CENTER OF GRAVITY
IMPORTANT - ALL
PANELS MUST BE IN
PLACE FOR RIGGING.
FIGURE 2
1- Detach wooden base protection before rigging.
2- Remove all six base protection brackets before
setting unit.
3- Connect rigging to the unit base using both holes in
each corner.
4- All panels must be in place for rigging.
5- Place field‐provided H‐style pick in place just above
top edge of unit. Frame must be of adequate
strength and length. (H-style pick prevents damage
to unit.)

Horizontal Air Discharge

Unit is shipped with panels covering the horizontal supply
and return air openings. Remove horizontal covers and
place over downflow openings for horizontal air discharge.
See figure 3. Secure in place with sheet metal screws.

Units Equipped With An Optional Economizer

1- Remove the horizontal supply air cover and position
over the downflow supply air opening. Secure with
sheet metal screws.
KG/KC 024, 030, 036, 048, 060, 072, 074, 090
*WEIGHT
LBS.
KG.
883
401
862
391
CAUTION - Do not
walk on unit.
2- Leave the horizontal return air cover in place.
3- Locate the separately ordered horizontal air
discharge kit. Place the kit panel over the downflow
return air opening.
4- Remove and retain the barometric relief dampers and
lower hood.
5- Install return air duct beneath outdoor air intake. See
figure 4. Install barometric relief damper in lower
hood and install in ductwork as shown in figure 4.
UNIT SUPPLY AND RETURN AIR OPENINGS
HORIZONTAL
SUPPLY AIR
HORIZONTAL
RETURN AIR
OPENING
DOWNFLOW
RETURN AIR
OPENING
HORIZONTAL RETURN AIR DUCTWORK
WITH ECONOMIZER
INSTALL BAROMETRIC RELIEF DAMPERS
AND HOOD IN RETURN AIR DUCT

Condensate Drains

Make drain connection to the 1" N.P.T. drain coupling
provided on unit.
Note - The drain pan is made with a glass reinforced
engineered plastic capable of withstanding typical joint
torque but can be damaged with excessive force. Tighten
pipe nipple hand tight and turn an additional quarter turn.
Page 6
OPENING
DOWNFLOW
SUPPLY AIR
OPENING
FIGURE 3
UNIT
UNIT
HORIZONTAL
RETURN AIR
DUCT
FIGURE 4

Hide quick links: