Condensate Side Drain Connection; Condensate Bottom Drain Connection; Units With Hinged Panels; Remove Drain Pan - Lennox KGB024 Installation Instructions Manual

Gas and cooling packaged units
Table of Contents

Advertisement

A trap must be installed between drain connection and an
open vent for proper condensate removal. See figure 5 or
6. It is sometimes acceptable to drain condensate onto
the roof or grade; however, a tee should be fitted to the
trap to direct condensate downward. The condensate line
must be vented. Check local codes concerning
condensate disposal. Refer to pages 1 and 2 for
condensate drain location.

CONDENSATE SIDE DRAIN CONNECTION

CAULK AROUND CONDENSATE COUPLING
NOTE - Allow clearance to
open doors when installing
condensate piping.
Minimum Pitch
OPEN VENT
1" (25 mm) per
10' (3 m) of line
Á Á
Á Á
Á Á
Á Á
Á Á
Á Á
Á Á
Á Á
Á Á Á Á Á Á Á Á Á Á Á Á
Á Á
FIGURE 5

CONDENSATE BOTTOM DRAIN CONNECTION

CONDENSATE COUPLING
MOUNTING
FRAME
FIGURE 6
Units are shipped with the drain coupling facing the front
of the unit. Condensate can be drained from the back or
bottom of the unit with the following modifications. The
unit can be installed in either downflow or horizontal air
discharge regardless of condensate drain location.
Rear Drain Connection
1- Remove the condensate drain mullion. See figure 7.
Remove the two panels on each side of the mullion.
UNIT
MOUNTING
FRAME
UNIT
DRAIN PAN
CAULK AROUND
OPEN VENT
Minimum Pitch
1" (25 mm) per 10'
(3 m) of line
If the unit has hinged panels, two hinge screws must
be removed in addition to the mullion screws. See
figure 8.

UNITS WITH HINGED PANELS

2- Lift the front edge of the drain pan and slide pan out
of unit. See figure 9.

REMOVE DRAIN PAN

3- Make sure the cap over the unit bottom drain hole is
secure.
4- Rotate the drain pan until the downward slope is
toward the back of the unit. Slide the drain pan back
into the unit. Be careful not to dislodge the cap over
the bottom drain hole.
5- From the back side of the unit, pull the drain pan
coupling through the rear condensate opening.
6- Replace the condensate drain mullion.
Page 7
CONDENSATE
DRAIN MULLION
FIGURE 7
CONDENSATE
DRAIN MULLION
REMOVE
TWO
SCREWS
FIGURE 8
DRAIN PAN
FIGURE 9
507348-04
12/2015