BLOWER DATA - DIRECT DRIVE - KGB024

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (larger gas heat section, economizer, wet coil, etc.) See page 41.
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
2 Ton Standard Efficiency (Downflow)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
2 Ton Standard Efficiency (Horizontal)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
High
Medium
1275
979
1262
960
1243
938
1218
909
1186
866
1137
838
1104
795
1055
752
990
694
925
637
794
523
1204
937
1186
913
1164
882
1137
860
1104
818
1070
775
1031
733
991
690
937
626
804
566
678
497
Low
High
878
1453
834
1440
790
1420
746
1396
710
1352
657
1316
604
1263
534
1210
463
1158
392
1070
290
928
818
1370
788
1352
748
1327
710
1300
670
1263
612
1227
554
1190
500
1136
432
1081
362
1009
287
900
Page 15
230 VOLTS
Medium
Low
KGB024S
1140
926
1124
912
1096
884
1065
853
1033
822
986
774
954
727
906
680
859
632
764
538
669
477
KGB024S
1098
879
1066
864
1034
839
1001
809
968
768
925
728
881
688
816
628
751
557
665
492
565
416