Blower Data - Direct Drive - Kga060 - Lennox KGB024 Installation Instructions Manual

Gas and cooling packaged units
Table of Contents

Advertisement

BLOWER DATA - DIRECT DRIVE - KGA060

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (larger gas heat section, economizer, wet coil, etc.) See page 41.
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
High
5 Ton Standard Efficiency (Downflow)
0.0
2200
0.1
2256
0.2
2202
0.3
2170
0.4
2158
0.5
2130
0.6
2056
0.7
2032
0.8
1963
0.9
1887
1.0
1695
5 Ton Standard Efficiency (Horizontal)
0.0
2114
0.1
2115
0.2
2074
0.3
2025
0.4
1996
0.5
1952
0.6
1882
0.7
1838
0.8
1773
0.9
1657
1.0
1548
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
Low
1649
1669
1739
1705
1689
1676
1662
1657
1591
1597
1400
1615
1610
1622
1599
1577
1542
1534
1488
1443
1389
1335
Page 18
230 VOLTS
High
Low
2411
1957
2417
2002
2396
1985
2328
1972
2293
1959
2279
1930
2158
1900
2089
1857
2077
1796
1876
1746
1746
1601
2305
1880
2290
1876
2249
1870
2188
1841
2148
1812
2087
1768
2026
1739
1966
1680
1905
1622
1784
1534
1672
1462
460/575 VOLTS
High
Low
KGA060S
2241
1755
2221
1742
2193
1747
2144
1725
2104
1695
2086
1678
2008
1652
1975
1610
1941
1586
1855
1555
1778
1486
KGA060S
2308
1890
2334
1906
2292
1890
2230
1859
2210
1846
2148
1817
2108
1786
2094
1743
1988
1682
1915
1679
1853
1506

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents