BLOWER DATA - DIRECT DRIVE - KGB060

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (larger gas heat section, economizer, wet coil, etc.) See page 41.
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
High
5 Ton Standard Efficiency (Downflow)
0.0
1940
0.1
1929
0.2
1906
0.3
1872
0.4
1836
0.5
1802
0.6
1749
0.7
1714
0.8
1644
0.9
1574
1.0
1338
5 Ton Standard Efficiency (Horizontal)
0.0
1930
0.1
1920
0.2
1910
0.3
1870
0.4
1840
0.5
1790
0.6
1739
0.7
1679
0.8
1639
0.9
1559
1.0
1438
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
Low
1581
1566
1552
1546
1526
1486
1447
1407
1347
1245
- - -
1575
1573
1576
1552
1524
1495
1466
1428
1371
1270
- - -
230 VOLTS
High
Low
2131
1788
2107
1784
2074
1774
2036
1752
1998
1708
1960
1679
1904
1635
1847
1576
1771
1518
1658
1430
1506
- - -
2143
1764
2115
1761
2088
1751
2055
1746
2023
1704
1979
1675
1925
1633
1860
1590
1775
1534
1670
1421
1539
1285
Page 19
460/575 VOLTS
High
Low
KGB060S
2131
1788
2107
1784
2074
1774
2036
1752
1998
1708
1960
1679
1904
1635
1847
1576
1771
1518
1658
1430
1506
- - -
KGB060S
2143
1764
2115
1761
2088
1751
2055
1746
2023
1704
1979
1675
1925
1633
1860
1590
1775
1534
1670
1421
1539
1285