Four Way Valve Performance Check; Inverter Unit Refrigerant System Check - Daikin FTX09NMVJU Service Manual

Hide thumbs Also See for FTX09NMVJU:
Table of Contents

Advertisement

SiUS091601E
5.5

Four Way Valve Performance Check

Check No.13
5.6

Inverter Unit Refrigerant System Check

Check No.14
Service Diagnosis
Turn the power off and then on
again.
Start heating operation.
S80
voltage at 208 - 230
VAC with compressor
on? (Fig. 1)
YES
Disconnect the four way valve coil
from the connector and check the
continuity.
Four way
valve coil resistance at
1000 ~ 2000 Ω?
YES
(Fig. 1)
Voltage at S80
208 - 230 VAC
Compressor
ON
Refrigerant system check
Is the
discharge pipe
thermistor disconnected
from the holder?
NO
Check for refrigerant leakage.
See the service diagnosis on
refrigerant shortage (U0).
∗ Four way valve coil
Cooling / Dry / Defrost: Not energized
Heating: energized
NO
NO
Time
(R14674)
YES
Check
Replace the outdoor unit
PCB (main PCB).
Replace the four way valve
coil.
Replace the four way valve.
(R21674)
Reconnect the thermistor.
Replace the refrigerant.
(R15833)
104

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents