Daikin FTK09NMVJU Engineering Data

Daikin FTK09NMVJU Engineering Data

Cooling only / heat pump - seer 18 models
Hide thumbs Also See for FTK09NMVJU:

Advertisement

EDUS041502
Split Type Air Conditioners
- Cooling Only / Heat Pump -
SEER 18 Models
FTK(X)-N Series

Advertisement

Table of Contents
loading

Summary of Contents for Daikin FTK09NMVJU

  • Page 1 EDUS041502 Split Type Air Conditioners - Cooling Only / Heat Pump - SEER 18 Models FTK(X)-N Series...
  • Page 3: Table Of Contents

    EDUS041502 Split Type Air Conditioners FTK(X)-N Series FTK09NMVJU RK09NMVJU FTK12NMVJU RK12NMVJU Cooling Only FTK18NMVJU RK18NMVJU FTK24NMVJU RK24NMVJU FTX09NMVJU RX09NMVJU FTX12NMVJU RX12NMVJU Heat Pump FTX18NMVJU RX18NMVJU FTX24NMVJU RX24NMVJU 1. Power Supply ....................3 2. Functions..................... 4 3. Specifications ....................6 3.1 Cooling Only....................6 3.2 Heat Pump ....................
  • Page 4 EDUS041502 11.Installation Manual ..................54 11.1 Indoor Unit....................54 11.2 Outdoor Unit ....................66 12.Operation Manual..................78 12.1 Cooling Only....................78 12.2 Heat Pump ....................106 13.Optional Accessories ................134 13.1 Option List ....................134 13.2 <BRC944B2> Wired Remote Controller........... 135 13.3 <KRC72A> Centralized Control Board-Up to 5 Rooms......149 13.4 <KRP413AB1S>...
  • Page 5: Power Supply

    EDUS041502 Power Supply 1. Power Supply Indoor Unit Outdoor Unit Power Supply FTK09NMVJU RK09NMVJU FTK12NMVJU RK12NMVJU FTK18NMVJU RK18NMVJU FTK24NMVJU RK24NMVJU 1 phase, 208 - 230 V, 60 Hz FTX09NMVJU RX09NMVJU FTX12NMVJU RX12NMVJU FTX18NMVJU RX18NMVJU FTX24NMVJU RX24NMVJU Note: Power Supply Intake; Outdoor Unit...
  • Page 6: Functions

    Functions EDUS041502 2. Functions Category Functions Category Functions Basic Inverter (with inverter power control) Health & Air-purifying filter — — Function Clean 10 ~ 10 ~ Photocatalytic deodorizing filter — — Operation limit for cooling (°CDB) Air-purifying filter with photocatalytic —...
  • Page 7 EDUS041502 Functions Category Functions Category Functions Basic Inverter (with inverter power control) Health & Air-purifying filter — — Function Clean 10 ~ 10 ~ Photocatalytic deodorizing filter — — Operation limit for cooling (°CDB) Air-purifying filter with photocatalytic — — 50 ~ 50 ~ deodorizing function...
  • Page 8: Specifications

    Specifications EDUS041502 3. Specifications Cooling Only 60 Hz, 208 - 230 V Indoor Unit FTK09NMVJU FTK12NMVJU Model Outdoor Unit RK09NMVJU RK12NMVJU 2.64 (1.30 ~ 3.00) 3.20 (1.30 ~ 3.90) Capacity Btu/h 9,000 (4,400 ~ 10,200) 10,900 (4,400 ~ 13,300) Rated (Min. ~ Max.)
  • Page 9 EDUS041502 Specifications 60 Hz, 208 - 230 V Indoor Unit FTK18NMVJU FTK24NMVJU Model Outdoor Unit RK18NMVJU RK24NMVJU 5.28 (1.60 ~ 5.86) 6.20 (1.60 ~ 7.03) Capacity Btu/h 18,000 (5,500 ~ 20,000) 21,200 (5,500 ~ 24,000) Rated (Min. ~ Max.) kcal/h 4,540 (1,380 ~ 5,040) 5,330 (1,380 ~ 6,050) Moisture Removal...
  • Page 10: Heat Pump

    Specifications EDUS041502 Heat Pump 60 Hz, 208 - 230 V Indoor Unit FTX09NMVJU FTX12NMVJU Model RX09NMVJU RX12NMVJU Outdoor Unit Cooling Heating Cooling Heating 2.64 (1.30 ~ 3.00) 2.93 (1.30 ~ 3.80) 3.20 (1.30 ~ 3.90) 3.96 (1.30 ~ 4.80) Capacity Btu/h 9,000 (4,400 ~ 10,200) 10,000 (4,400 ~ 13,000)
  • Page 11 EDUS041502 Specifications 60 Hz, 208 - 230V Indoor Unit FTX18NMVJU FTX24NMVJU Model RX18NMVJU RX24NMVJU Outdoor Unit Cooling Heating Cooling Heating 5.28 (1.60 ~ 5.86) 6.33 (1.60 ~ 7.03) 6.20 (1.60 ~ 7.03) 7.03 (1.70 ~ 8.10) Capacity Btu/h 18,000 (5,500 ~ 20,000) 21,600 (5,500 ~ 24,000) 21,200 (5,500 ~ 24,000) 24,000 (5,800 ~ 27,600)
  • Page 12: Dimensions

    Dimensions EDUS041502 4. Dimensions Indoor Unit 4.1.1 Cooling Only FTK09/12NMVJU INCLUDING AIR FLOW ( INDOOR ) REQUIRED SPACE THE MARK (→) SHOWS PIPING DIRECTION MOUNTING PLATE 8-7/8 ( 225 mm ) REAR 30-5/16 ( 770 mm ) 8-3/4 ( 223 mm ) RIGHT LEFT GENERAL RATING...
  • Page 13 EDUS041502 Dimensions FTK24NMVJU THE MARK (→) SHOWS PIPING DIRECTION AIR FLOW (INDOOR) 39 (990mm) REAR LEFT RIGHT INCLUDING MOUNTING PLATE 10-7/16 (265mm) 1-15/16 (50mm) MIN 10-3/8 (263mm) 1-15/16 (50mm) MIN (SPACE FOR REQUIRED SPACE GENERAL RATING MAINTENANCE) (SPACE FOR NAME PLATE MAINTENANCE) TERMINAL BLOCK WITH EARTH...
  • Page 14 Dimensions EDUS041502 FTX18NMVJU THE MARK (→) SHOWS PIPING DIRECTION AIR FLOW ( INDOOR ) 39 ( 990mm ) REAR RIGHT LEFT INCLUDING MOUNTING PLATE 10-7/16 ( 265mm ) 1-15/16 ( 50mm ) MIN 10-3/8 ( 263mm ) 1-15/16 ( 50mm ) MIN (SPACE FOR REQUIRED SPACE GENERAL RATING...
  • Page 15: Outdoor Unit

    EDUS041502 Dimensions Outdoor Unit RK09/12NMVJU, RX09/12NMVJU 18-1/2 (470) 3-13/16 (97) 16-1/16 (408) DRAIN OUTLET (I.D.φ5/8 (φ15.9mm) HOSE FOR CONNECTION WITH DRAIN JOINT) 4-HOLES FOR FOUNDATION BOLTS (M8 OR M10) OUTDOOR AIR THERMISTOR 9/16 (15) 26-9/16 (675) 1-5/16 (50) 5/16 (8) LIQUID HANDLE STOP VALVE...
  • Page 16 Dimensions EDUS041502 RK24NMVJU, RX24NMVJU HANDLE 9/16 ( 14 ) 34-1/4 ( 870 ) 2-3/4 ( 70 ) OUTDOOR AIR THERMISTOR 1/4 ( 7 ) 12-5/8 ( 320 ) 1-3/16 ( 30 ) ELECTRIC WIRE INTAKE BRAND NAME PLATE MANUFACTURER'S LABEL 3/4 ( 19 ) 7/8 ( 23 ) 9/16 ( 14.5 )
  • Page 17: Wiring Diagrams

    EDUS041502 Wiring Diagrams 5. Wiring Diagrams Indoor Unit FTK09/12NMVJU, FTX09/12NMVJU PCB2 PCB1 FIELD WIRING. MR10 LED1 TRANSMISSION GRN/YLW CIRCUIT MR10 LED2 OUTDOOR RECTIFIER t˚ FU1 3.15A SIGNAL RECEIVER CAUTION IPM200 NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK S403 ON AGAIN.
  • Page 18: Outdoor Unit

    Wiring Diagrams EDUS041502 Outdoor Unit RK09/12NMVJU, RX09/12NMVJU IPM1 MRM10 L2 2 HN1 V2 C400 INDOOR C405 MR30 V150 3.15A 3.15A POWER SUPPLY MRCW FIELD WIRING. OUTDOOR PCB1 NOTE 1. REFER TO THE NAME PLATE FOR THE POWER t˚ t˚ t˚ IN CASE OF REQUIREMENTS.
  • Page 19: Piping Diagrams

    EDUS041502 Piping Diagrams 6. Piping Diagrams Indoor Unit 6.1.1 Cooling Only FTK09/12NMVJU FTK18NMVJU INDOOR UNIT INDOOR UNIT HEAT EXCHANGER 1/4 CuT DISTRIBUTOR HEAT EXCHANGER THERMISTOR ON HEAT EXCH. THERMISTOR CROSS FLOW FAN ON HEAT EXCH. FIELD PIPING FIELD PIPING CROSS FLOW FAN 1/4 CuT ( 1/4 CuT ) SINGLE UNION...
  • Page 20 Piping Diagrams EDUS041502 6.1.2 Heat Pump FTX09/12NMVJU FTX18NMVJU INDOOR UNIT INDOOR UNIT HEAT EXCHANGER 1/4 CuT DISTRIBUTOR HEAT EXCHANGER THERMISTOR ON HEAT EXCH. THERMISTOR CROSS FLOW FAN ON HEAT EXCH. FIELD PIPING FIELD PIPING CROSS FLOW FAN 1/4 CuT ( 1/4 CuT ) SINGLE UNION JOINT FAN MOTOR...
  • Page 21: Outdoor Unit

    EDUS041502 Piping Diagrams Outdoor Unit 6.2.1 Cooling Only RK09NMVJU OUTDOOR UNIT OUTDOOR TEMPERATURE HEAT EXCHANGER THERMISTOR 9/32 CuT 9/32 CuT HEAT EXCHANGER THERMISTOR 1/4 CuT 1/4 CuT 9/32 CuT MUFFLER WITH MOTOR FILTER OPERATED PROPELLER FAN VALVE MUFFLER WITH 3/8 CuT FILTER FOUR WAY VALVE...
  • Page 22 Piping Diagrams EDUS041502 RK18NMVJU OUTDOOR UNIT HEAT EXCHANGER OUTDOOR AIR 9/32 CuT THERMISTOR 9/32 CuT 9/32 CuT CAPILLARY TUBE 1 9/32 CuT 5/32 CuT 1/4 CuT 1/4 CuT CAPILLARY TUBE 2 REFRIGERANT FLOW 5/32 CuT COOLING MUFFLER WITH HEAT EXCHANGER FILTER THERMISTOR ELECTRONIC...
  • Page 23 EDUS041502 Piping Diagrams 6.2.2 Heat Pump RX09NMVJU OUTDOOR UNIT OUTDOOR TEMPERATURE HEAT EXCHANGER THERMISTOR 9/32 CuT 9/32 CuT HEAT EXCHANGER THERMISTOR 1/4 CuT 1/4 CuT 9/32 CuT MUFFLER WITH MOTOR FILTER OPERATED PROPELLER FAN VALVE MUFFLER WITH 3/8 CuT FILTER FOUR WAY VALVE FIELD PIPING...
  • Page 24 Piping Diagrams EDUS041502 RX18NMVJU OUTDOOR UNIT HEAT EXCHANGER OUTDOOR AIR 9/32 CuT THERMISTOR 9/32 CuT 9/32 CuT CAPILLARY TUBE 1 9/32 CuT 5/32 CuT 1/4 CuT 1/4 CuT CAPILLARY TUBE 2 REFRIGERANT FLOW 5/32 CuT COOLING MUFFLER HEATING WITH FILTER HEAT EXCHANGER THERMISTOR ELECTRONIC...
  • Page 25: Capacity Tables

    EDUS041502 Capacity Tables 7. Capacity Tables Cooling Only FTK09NMVJU + RK09NMVJU 11.8 0.22 60 Hz, 208 V Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 2.70 2.27 0.55 2.58 2.21 0.61 2.46 2.15 0.66 2.41...
  • Page 26 Capacity Tables EDUS041502 Symbols: Notes: : Airflow rate /min.) shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the : Bypass factor above tables. (Figures out of the tables should not be used for calculation.) 3.
  • Page 27 EDUS041502 Capacity Tables FTK12NMVJU + RK12NMVJU 12.3 0.16 60 Hz, 208 V Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 3.28 2.66 0.67 3.13 2.59 0.74 2.98 2.52 0.80 2.92 2.49 0.83 2.83 2.45 0.86 2.68 2.38...
  • Page 28 Capacity Tables EDUS041502 Symbols: Notes: : Airflow rate /min.) shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the : Bypass factor above tables. (Figures out of the tables should not be used for calculation.) 3.
  • Page 29 EDUS041502 Capacity Tables FTK18NMVJU + RK18NMVJU 20.2 0.27 60 Hz, 208 V Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 5.41 4.15 1.11 5.16 4.03 1.21 4.92 3.91 1.32 4.82 3.86 1.36 4.67 3.79 1.43 4.43 3.67...
  • Page 30 Capacity Tables EDUS041502 Symbols: Notes: : Airflow rate /min.) shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the : Bypass factor above tables. (Figures out of the tables should not be used for calculation.) 3.
  • Page 31 EDUS041502 Capacity Tables FTK24NMVJU + RK24NMVJU 20.2 0.27 60 Hz, 208 V Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 6.05 4.47 1.29 6.05 4.47 1.43 5.77 4.33 1.55 5.66 4.27 1.60 5.49 4.19 1.68 5.20 4.04...
  • Page 32 Capacity Tables EDUS041502 Symbols: Notes: : Airflow rate /min.) shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the : Bypass factor above tables. (Figures out of the tables should not be used for calculation.) 3.
  • Page 33: Heat Pump

    EDUS041502 Capacity Tables Heat Pump FTX09NMVJU + RX09NMVJU 60 Hz, 208 V Cooling 11.8 0.22 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 2.70 2.27 0.55 2.58 2.21 0.61 2.46 2.15 0.66 2.41 2.13 0.68 2.34 2.10...
  • Page 34 Capacity Tables EDUS041502 60 Hz, 230 V Cooling 11.8 0.22 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 2.70 2.27 0.55 2.58 2.21 0.61 2.46 2.15 0.66 2.41 2.13 0.68 2.34 2.10 0.71 2.21 2.04 0.77 16.0...
  • Page 35 EDUS041502 Capacity Tables Symbols: Notes: : Airflow rate /min.) shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the : Bypass factor above tables. (Figures out of the tables should not be used for calculation.) 3.
  • Page 36 Capacity Tables EDUS041502 FTX12NMVJU + RX12NMVJU 60 Hz, 208 V Cooling 12.3 0.16 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 3.28 2.66 0.67 3.13 2.59 0.74 2.98 2.52 0.80 2.92 2.49 0.83 2.83 2.45 0.86 2.68...
  • Page 37 EDUS041502 Capacity Tables 60 Hz, 230 V Cooling 12.3 0.16 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 3.28 2.66 0.67 3.13 2.59 0.74 2.98 2.52 0.80 2.92 2.49 0.83 2.83 2.45 0.86 2.68 2.38 0.93 16.0...
  • Page 38 Capacity Tables EDUS041502 Symbols: Notes: : Airflow rate /min.) shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the : Bypass factor above tables. (Figures out of the tables should not be used for calculation.) 3.
  • Page 39 EDUS041502 Capacity Tables FTX18NMVJU + RX18NMVJU 60 Hz, 208 V Cooling 20.2 0.27 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 5.41 4.15 1.11 5.16 4.03 1.21 4.92 3.91 1.32 4.82 3.86 1.36 4.67 3.79 1.43 4.43...
  • Page 40 Capacity Tables EDUS041502 60 Hz, 230 V Cooling 20.2 0.27 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 5.41 4.15 1.11 5.16 4.03 1.21 4.92 3.91 1.32 4.82 3.86 1.36 4.67 3.79 1.43 4.43 3.67 1.53 16.0...
  • Page 41 EDUS041502 Capacity Tables Symbols: Notes: : Airflow rate /min.) shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the : Bypass factor above tables. (Figures out of the tables should not be used for calculation.) 3.
  • Page 42 Capacity Tables EDUS041502 FTX24NMVJU + RX24NMVJU 60 Hz, 208 V Cooling 20.2 0.27 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 6.05 4.47 1.29 6.05 4.47 1.43 5.77 4.33 1.55 5.66 4.27 1.60 5.49 4.19 1.68 5.20...
  • Page 43 EDUS041502 Capacity Tables 60 Hz, 230 V Cooling 20.2 0.27 Temp: Celsius TC, SHC, PI: kW INDOOR OUTDOOR TEMPERATURE (°CDB) °C °C 14.0 20.0 6.05 4.47 1.29 6.05 4.47 1.43 5.77 4.33 1.55 5.66 4.27 1.60 5.49 4.19 1.68 5.20 4.04 1.71 16.0...
  • Page 44 Capacity Tables EDUS041502 Symbols: Notes: : Airflow rate /min.) shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the : Bypass factor above tables. (Figures out of the tables should not be used for calculation.) 3.
  • Page 45 EDUS041502 Capacity Tables Capacity Correction Factor by the Length of Refrigerant Piping (Reference) The cooling capacity and the heating capacity of the unit have to be corrected in accordance with the length of refrigerant piping — the distance between the indoor unit and the outdoor unit. <—...
  • Page 46 Capacity Tables EDUS041502 7.3.3 24 Class (R-410A) Range of the refrigerant additional charge 16.4 32.8 49.2 65.6 82.0 98.4 (ft) 30 (m) Piping length Note: The graphs show the factor when additional refrigerant of the proper quantity is charged. Split Type Air Conditioners FTK(X)-N Series...
  • Page 47: Operation Limit

    EDUS041502 Operation Limit 8. Operation Limit RK09/12/18/24NMVJU Cooling 114.8 57.2 68 73.4 82.4 Indoor temp. (˚FWB) Notes: The graphs are based on the following conditions. • Equivalent piping length 25ft • Level difference 4D092212 • Air flow rate High RX09/12/18/24NMVJU Cooling Heating 64.4...
  • Page 48: Sound Level

    Sound Level EDUS041502 9. Sound Level Measuring Location Indoor Unit Outdoor 3.3 ft 3.3 ft (1 m) (1 m) MICROPHONE MICROPHONE Notes: 1. Operation sound is measured in an anechoic chamber. 2. The data are based on the conditions shown in the table below. Cooling Heating Piping Length...
  • Page 49: Indoor Unit

    EDUS041502 Sound Level Indoor Unit 9.2.1 Cooling Only FTK09NMVJU FTK12NMVJU OVER ALL ( dB ) OVER ALL ( dB ) NC-70 NC-70 60Hz 60Hz 60Hz 60Hz SCALE 208/230V 208/230V SCALE 208/230V 208/230V ( H ) ( L ) ( H )
  • Page 50 Sound Level EDUS041502 9.2.2 Heat Pump FTX09NMVJU COOLING HEATING OVER ALL ( dB ) OVER ALL ( dB ) NC-70 NC-70 60Hz 60Hz 60Hz 60Hz SCALE 208/230V 208/230V SCALE 208/230V 208/230V ( H ) ( L ) ( H ) ( L ) NC-60 NC-60...
  • Page 51 EDUS041502 Sound Level FTX24NMVJU COOLING HEATING NC-70 NC-70 60Hz 60Hz 60Hz 60Hz SCALE 208/230V 208/230V SCALE 208/230V 208/230V ( H ) ( L ) ( H ) ( L ) NC-60 NC-60 ( B.G.N IS ALREADY RECTIFIED ) ( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS OPERATING CONDITIONS NC-50...
  • Page 52: Outdoor Unit

    Sound Level EDUS041502 Outdoor Unit 9.3.1 Cooling Only RK09NMVJU RK12NMVJU COOLING COOLING OVER ALL ( dB ) OVER ALL ( dB ) NC-70 NC-70 SCALE 208-230V 60Hz SCALE 208-230V 60Hz NC-60 NC-60 ( B.G.N IS ALREADY RECTIFIED ) ( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS OPERATING CONDITIONS NC-50...
  • Page 53 EDUS041502 Sound Level 9.3.2 Heat Pump RX09NMVJU COOLING HEATING OVER ALL ( dB ) OVER ALL ( dB ) NC-70 NC-70 SCALE 208-230V 60Hz SCALE 208-230V 60Hz NC-60 NC-60 ( B.G.N IS ALREADY RECTIFIED ) ( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS OPERATING CONDITIONS NC-50...
  • Page 54 Sound Level EDUS041502 RX24NMVJU COOLING HEATING OVER ALL ( dB ) OVER ALL ( dB ) NC-70 NC-70 SCALE 208-230V 60Hz SCALE 208-230V 60Hz NC-60 NC-60 ( B.G.N IS ALREADY RECTIFIED ) ( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS OPERATING CONDITIONS NC-50 NC-50...
  • Page 55: Electric Characteristics

    10. Electric Characteristics Unit Combination Power Supply Compressor Indoor Unit Outdoor Unit Hz - Volts Voltage Range 60 - 208 Min. 187 V FTK09NMVJU RK09NMVJU 12.1 0.13 0.20 Max. 253 V 60 - 230 60 - 208 Min. 187 V FTK12NMVJU RK12NMVJU 12.2...
  • Page 56: Installation Manual

    Installation Manual EDUS041502 11. Installation Manual 11.1 Indoor Unit Split Type Air Conditioners FTK(X)-N Series...
  • Page 57 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 58 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 59 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 60 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 61 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 62 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 63 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 64 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 65 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 66 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 67 EDUS041502 Installation Manual 3P379970-1 Split Type Air Conditioners FTK(X)-N Series...
  • Page 68: Outdoor Unit

    Installation Manual EDUS041502 11.2 Outdoor Unit Split Type Air Conditioners FTK(X)-N Series...
  • Page 69 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 70 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 71 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 72 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 73 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 74 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 75 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 76 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 77 EDUS041502 Installation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 78 Installation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 79 EDUS041502 Installation Manual 3P379970-2A Split Type Air Conditioners FTK(X)-N Series...
  • Page 80: Operation Manual

    Operation Manual EDUS041502 12. Operation Manual 12.1 Cooling Only Split Type Air Conditioners FTK(X)-N Series...
  • Page 81 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 82 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 83 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 84 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 85 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 86 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 87 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 88 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 89 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 90 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 91 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 92 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 93 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 94 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 95 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 96 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 97 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 98 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 99 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 100 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 101 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 102 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 103 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 104 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 105 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 106 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 107 EDUS041502 Operation Manual 3P379751-2A Split Type Air Conditioners FTK(X)-N Series...
  • Page 108: Heat Pump

    Operation Manual EDUS041502 12.2 Heat Pump Split Type Air Conditioners FTK(X)-N Series...
  • Page 109 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 110 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 111 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 112 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 113 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 114 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 115 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 116 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 117 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 118 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 119 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 120 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 121 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 122 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 123 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 124 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 125 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 126 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 127 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 128 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 129 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 130 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 131 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 132 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 133 EDUS041502 Operation Manual Split Type Air Conditioners FTK(X)-N Series...
  • Page 134 Operation Manual EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 135 EDUS041502 Operation Manual 3P379751-1A Split Type Air Conditioners FTK(X)-N Series...
  • Page 136: Optional Accessories

    Optional Accessories EDUS041502 13. Optional Accessories 13.1 Option List 13.1.1 Indoor Unit Option Name 09/12 Class 18/24 Class BRC944B2 BRC944B2 Wired remote controller ★ 1 +KRP067A41 +KRP980B2 Length 9.8 ft (3 m) BRCW901A03 Wired remote controller cord (shielded wire) Length 26.3 ft (8 m) BRCW901A08 Centralized control board-up to 5 rooms ★...
  • Page 137: Brc944B2> Wired Remote Controller

    EDUS041502 Optional Accessories 13.2 <BRC944B2> Wired Remote Controller 13.2.1 Installation Manual CAUTION 1. No switch box or staple is supplied. Prepare them locally. 2. No remote controller cord is supplied. Prepare the optional remote controller cord 4 wire. 3. Be sure to turn off the power to any apparatus connected prior to mounting. 4.
  • Page 138 Optional Accessories EDUS041502 2. Securing the remote control adapter Double-face adhesive tape Remove the upper case of the remote control adapter and secure the lower case assembly. Wood screws (φ3.5mm x 16mm) (Mounting with supplied wood screws) (Mounting with supplied double-face adhesive tape) 3.
  • Page 139 EDUS041502 Optional Accessories 13.2.2 Operation Manual Controller Commands and their Corresponding Functions Run indicator lamp (green) ON/OFF button Display Press to start the system. Displays the operating Displays the operating Press again to stop the system. conditions. conditions. Timer select button Mode select button Selects one of the following: ONE TIME timer ON...
  • Page 140: Preparation Before Operation

    Optional Accessories EDUS041502 Preparation before Operation Checking the power If nothing appears on the remote controller's display, turn on the circuit breaker. Setting the current time Press The current time starts blinking. lights up. 1 · 3 Press and set the current time. Hold the button down to rapidly advance the time.
  • Page 141 EDUS041502 Optional Accessories Preparation before Operation Setting Temperature Indication change Temperature indication can be changed between Celsius and Fahrenheit before use. To change from Celsius temperature indication to Fahrenheit one Press and hold down at the same time for 5 seconds while the Celsius temperature is indicated.
  • Page 142 Optional Accessories EDUS041502 Automatic · DRY · Cooling · Heating Operation Select your desired operation mode. Once preset, the system can get restarted in the same operation mode. Run indicator lamp (green) Press to select your desired operation mode. Each time the button is pressed, the mode changes as follows.
  • Page 143 EDUS041502 Optional Accessories To adjust the temperature and airflow rate: Operation Automatic Cooling Heating mode Setting to be adjusted Temperature is adjustable. Temperature Recommended temperature cannot be Cooling : 26˚C-28˚C (79˚F~82˚F) adjusted. Heating : 20˚C-22˚C (68˚F~72˚F) (Temperature) Five levels of airflow rate setting from "...
  • Page 144: Adjusting Airflow Direction

    Optional Accessories EDUS041502 Adjusting Airflow Direction Adjust the airflow direction for maximum comfort. To adjust the Airflow Direction Press during operation . Each time the button is pressed, the airflow direction louvers change their movement. Wall Mounted Types (without horizontal swing function) The horizontal airflow direction louvers Swing move up and down.
  • Page 145 EDUS041502 Optional Accessories Wall Mounted Type (with horizontal swing function) The horizontal airflow direction louvers Swing horizontally move up and down. The horizontal airflow direction louvers Swing vertically stop just when the button is pressed. Then the vertical ones start moving right and left.
  • Page 146: Timer Operation

    Optional Accessories EDUS041502 Timer Operation The Timer Operation feature automatically turns off operation when you go to sleep and turns it back on when you wake up. Use the DAILY Timer mode on weekdays, and the ONE TIME timer mode on weekends. To select the ONE TIME timer mode: Press...
  • Page 147 EDUS041502 Optional Accessories ONE TIME timer Once the timer has been activated and then deactivated, it is in the OFF mode. The ON or OFF timers can be programmed. Press to select the ONE TIME timer. Press blinks. ONE TIME light up.
  • Page 148 Optional Accessories EDUS041502 Timer Operation To select the DAILY timer mode: Timers Two pairs of ON and OFF time Press to select the DAILY timer mode. settings can be programmed. Each time the button is pressed, the modes change as follows. ONE TIME timer ON time 24-hour timer display...
  • Page 149: Daily Timer

    EDUS041502 Optional Accessories DAILY timer After programming, the system starts and stops each day at the preset times. Two pairs of time settings can be programmed. (Example: 8:00 10:00, and 18:00 23:00) DAILY timer indication appears. lights up. Press to select the DAILY timer. Make the ON and OFF time settings.
  • Page 150 Optional Accessories EDUS041502 Cleaning Cleaning the remote controller Wipe it clean with soft, dry cloth. Do not use any water hotter than 40˚C (104˚F), or v olatile liquids such as benzine, gasoline and thinner, polishing powder, or anything hard such as a scrub brush. When the unit is not used for a long time 1 On a sunny day, keep the system running for half a day in the FAN mode to dry it up inside.
  • Page 151: Krc72A> Centralized Control Board-Up To 5 Rooms

    EDUS041502 Optional Accessories 13.3 <KRC72A> Centralized Control Board-Up to 5 Rooms Split Type Air Conditioners FTK(X)-N Series...
  • Page 152 Optional Accessories EDUS041502 3P169427-1 Split Type Air Conditioners FTK(X)-N Series...
  • Page 153: Krp413Ab1S> Wiring Adaptor For Timer Clock / Remote Controller

    EDUS041502 Optional Accessories 13.4 <KRP413AB1S> Wiring Adaptor for Timer Clock / Remote Controller Split Type Air Conditioners FTK(X)-N Series...
  • Page 154 Optional Accessories EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 155 EDUS041502 Optional Accessories Split Type Air Conditioners FTK(X)-N Series...
  • Page 156 Optional Accessories EDUS041502 3P248024-2 Split Type Air Conditioners FTK(X)-N Series...
  • Page 157: Krp928Bb2S> Interface Adaptor For Diii-Net (Residential Air Conditioner)

    EDUS041502 Optional Accessories 13.5 <KRP928BB2S> Interface Adaptor for DIII-NET (Residential Air Conditioner) Split Type Air Conditioners FTK(X)-N Series...
  • Page 158 Optional Accessories EDUS041502 3P248024-1D Split Type Air Conditioners FTK(X)-N Series...
  • Page 159 EDUS041502 Optional Accessories 3P248024-3D Split Type Air Conditioners FTK(X)-N Series...
  • Page 160: Krp067A41> Interface Adaptor For Residential Air Conditioner

    Optional Accessories EDUS041502 13.6 <KRP067A41> Interface Adaptor for Residential Air Conditioner Split Type Air Conditioners FTK(X)-N Series...
  • Page 161 EDUS041502 Optional Accessories Split Type Air Conditioners FTK(X)-N Series...
  • Page 162 Optional Accessories EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 163 EDUS041502 Optional Accessories 1P398933-1 Split Type Air Conditioners FTK(X)-N Series...
  • Page 164: Krp980B2> Interface Adaptor For Residential Air Conditioner

    Optional Accessories EDUS041502 13.7 <KRP980B2> Interface Adaptor for Residential Air Conditioner Split Type Air Conditioners FTK(X)-N Series...
  • Page 165 EDUS041502 Optional Accessories Split Type Air Conditioners FTK(X)-N Series...
  • Page 166 Optional Accessories EDUS041502 Split Type Air Conditioners FTK(X)-N Series...
  • Page 167 EDUS041502 Optional Accessories 3P363899-2C Split Type Air Conditioners FTK(X)-N Series...
  • Page 168: Kpw937E4> Air Direction Adjustment Grille

    Optional Accessories EDUS041502 13.8 <KPW937E4> Air Direction Adjustment Grille Split Type Air Conditioners FTK(X)-N Series...
  • Page 169 EDUS041502 Optional Accessories 3P397163-1 Split Type Air Conditioners FTK(X)-N Series...
  • Page 170: Kpw063A4> Air Direction Adjustment Grille

    Optional Accessories EDUS041502 13.9 <KPW063A4> Air Direction Adjustment Grille Split Type Air Conditioners FTK(X)-N Series...
  • Page 171 EDUS041502 Optional Accessories 3P398171-1 Split Type Air Conditioners FTK(X)-N Series...
  • Page 176 Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.