Daikin FTX09NMVJU Service Manual page 102

Hide thumbs Also See for FTX09NMVJU:
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.01
Refer to P.101
Check No.12
Refer to P.103
Check No.17
Refer to P.108
Check No.18
Refer to P.108
Check No.19
Refer to P.109
91
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the installation space.
Check No. 17
Check the installation
condition.
OK
Check No. 19
Check the outdoor fan.
OK
Check No. 18
Check the discharge
pressure.
OK
Check No. 12
Check the electronic
expansion valve.
OK
Check No. 01
Check the outdoor heat
exchanger thermistor.
OK
NG
NG
NG
NG
NG
SiUS091601E
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
(R20418)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents