2.4 FASTENING THE BRACKET (P6)
Drill holes for anchoring the bracket to the
wall using the (6) holes shown in black on
the paper template.
The anchor bolts provided require (6) Ø5/16"
holes.
NOTICE: If the wall is not sturdy enough, it is
advisable to use extra anchor bolts using the
holes shown in grey on the paper template.
NOTICE:
The wall should be inspected to
determine if the manufacturer provided bolts are
adequate for the installation depending on the
application.
Due
variations, it may be necessary for the installing
contractor to use a different type of anchorage to
maintain the intended installation of the unit to the
wall. The manufacture is not liable in case of
underestimation of the structural consistency of
the anchorage made at the time of installation.
...........................................................................................................................
OWNER'S MANUAL
to
building
construction
Packaged Thru-The-Wall Heat Pump
2.5 INSTALLATION OF THE PIPES (P20)
Ø5-29/32"
After drilling the holes, the plastic pipes supplied
with the unit need to be fitted through them.
The pipe with a diameter of 6-5/16"in (air
discharge pipe) has to be fitted in the right
hole.
The length of the pipes should be same as
the depth of the wall plus 1/32". Use a
normal hacksaw to cut the supplied pipes to
the correct length. Remember that the
installation must have the same slope as the
hole (minimum 3 degrees). NOTE:
Because the tube diameter is nearly the
same as the Ø6-3/8" core drill, the fit will be
snug. A rubber hammer and a small piece
of wood can be used to gently tap the tube
into the hole.
Please use the same instructions to fit the
left hand tube (fresh air intake pipe) using
the Ø5-29/32"in supplied pipe.
Insert the Ø5-29/32"in ring into the space
between the wall and pipe.
Insert the fresh air pipe (Ø1-31/32") into the
Ф2-1/16" hole.
Please center the pipes into the holes in the
wall and insulate and seal their perimeters to
prevent air and humidity infiltration using
polyurethane foam and using plaster for
finishing the inside wall.
6
Ø1-31/32"
Ø6-5/16"