Figure 2.1 Refrigerant Sight Glass - Bard D25A2PA Installation And Service Instructions Manual

Table of Contents

Advertisement

This unit employs high-flow Coremax valves instead of
the typical Shrader type valves.
WARNING! Do NOT use a Schrader valve core removal
tool with these valves. Use of such a tool could result
in eye injuries or refrigerant burns!
Return Air
Model
Pressure
Temperature
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
D25A/L
67° WB
High Side
85° DB
Low Side
72° WB
High Side
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
D28A/L
67° WB
High Side
85° DB
Low Side
72° WB
High Side
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
D35A/L
67° WB
High Side
85° DB
Low Side
72° WB
High Side
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
D36A/L
67° WB
High Side
85° DB
Low Side
72° WB
High Side
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
D42A/L
67° WB
High Side
85° DB
Low Side
72° WB
High Side
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
D48A/L
67° WB
High Side
85° DB
Low Side
72° WB
High Side
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
D60A/L
67° WB
High Side
85° DB
Low Side
72° WB
High Side
Low Side Pressure ±4 PSIG
High Side Pressure ±10PSIG
The refrigerant sight glass installed in this unit is not a
charging indicator. The sight glass is for moisture reference
only. If charge is in doubt, reclaim, evacuate and recharge
the unit to the serial plate charge.
TABLE 2.1
Nominal Pressures
Air Temperature Entering Outdoor Coil, Degree °F
75
80
85
90
95
132
133
134
136
137
292
308
327
347
369
141
142
143
145
146
299
316
335
356
378
146
147
148
150
151
309
327
347
368
391
137
137
137
139
140
279
299
321
342
366
146
146
147
149
150
286
307
329
351
375
151
151
152
154
155
296
318
341
363
388
118
120
122
125
127
327
349
371
396
421
126
128
131
134
136
335
358
381
406
432
130
132
136
139
141
347
371
394
420
447
133
135
137
138
139
313
327
342
361
382
142
144
146
148
149
321
335
351
370
392
147
149
151
153
154
332
347
363
383
406
131
132
134
136
137
315
331
348
368
388
140
141
143
145
147
323
339
357
377
398
145
146
148
150
152
334
351
369
390
412
133
136
137
139
141
325
341
360
379
401
142
145
147
149
151
333
350
369
389
411
147
150
152
154
156
345
362
382
403
425
129
130
132
133
134
353
362
374
390
410
138
139
141
142
143
362
371
384
400
420
143
144
146
147
148
375
384
397
414
435
FIGURE 2.1
Refrigerant Sight Glass
To change a Coremax valve without first removing the
refrigerant, a special tool is required which can be
obtained at www.fastestinc.com/en/SCCA07H. See the
replacement parts manual for replacement core part
numbers.
100
105
110
115
138
140
142
144
392
417
445
474
148
150
152
154
402
428
456
486
153
155
157
159
416
443
472
503
141
143
144
146
389
413
439
464
151
153
154
156
399
424
450
476
156
158
159
161
413
439
466
493
129
132
134
136
448
475
504
533
138
141
143
145
459
487
517
547
143
146
148
150
475
504
535
566
141
143
145
147
406
432
461
492
151
153
155
157
416
443
473
505
156
158
160
162
431
459
490
523
139
142
144
146
410
435
461
489
149
152
154
156
421
446
473
502
154
157
159
161
436
462
490
520
142
144
145
147
424
449
477
505
152
154
155
157
435
461
489
518
157
159
160
162
450
477
506
536
136
137
137
139
432
458
488
522
145
146
147
149
443
470
501
535
150
151
152
154
459
486
519
554
Capacitors
120
Part No.
Ratings
147
1 Ø, 240V
505
8552-050
40+15/370
157
518
3 Ø, 240V
8552-002
162
5/370
536
148
1 Ø, 240V
491
8552-055
40+.10/370
158
504
3 Ø, 240V
8552-005
164
10/370
522
137
1 Ø, 240V
565
8552-052
45+15/370
147
579
3 Ø, 240V
8552-002
152
5/370
599
149
1 Ø, 240V
527
8552-079
45+10/370
159
540
3 Ø, 240V
8552-005
165
10/370
559
149
1 Ø, 240V
520
8552-079
45+10/370
159
533
3 Ø, 240V
8552-005
165
10/370
552
148
1 Ø, 240V
535
8552-089
70+10/370
158
549
3 Ø, 240V
8552-005
164
10/370
568
140
1 Ø, 240V
559
8552-058
80+10/440
150
573
3 Ø, 240V
8552-005
155
10/370
593
Manual 2100-643C