Select SHOW ALL from the History screen menu to display the Event History (All)
Log. The Event History (All) Log lists up to the 500 system events in chronological
order, with the most recent event listed last (once 500 is reached, the earliest event
is overwritten). The end of the log (the most recent events) appears when you
display the screen, and you must scroll upward to view older event listings. Figure
9---5 shows the Event History (All) Log screen.
To scroll through the events, select the
To return to the Simple History screen, select SIMPLE from the History (All) menu.
STATUS:
ALARM:
CMD:
CMD:
5 of 29
Select EVENTS from the Simple History or History (All) screen menu to display a
listing of all system events that are currently active. The most recent system event
is listed first. As events clear, they are removed from the Active System Events
listing. Figure 9---6 shows the Active System Events screen.
To scroll through the events, select the
To return to the History screen, select HISTORY from the Active Events menu.
ALARM:
ALARM:
NOTICE: BATTERY VOLTAGE LOW
NOTICE: NO SYNC ON
Powerware 9330 (IBM 9910 20 kVA) Installation and Operation
164201491 REV. B 013004
HISTORY (ALL)
CSB POWER SUPPLY ON
AC INPUT UNDER VOLTAGE
LOAD OFF COMMAND
NORMAL MODE COMMAND
06/20/2003
EVENTS
Figure 9 ---5. Event History (All) Log Screen
ACTIVE EVENTS
AC INPUT UNDERVOLTAGE
BYPASS UNDER VOLTAGE
Figure 9 ---6. Active System Events Screen
or
pushbuttons from the display menu.
10:20:03.539
SIMPLE
or
pushbuttons from the display menu.