Powerware 9330 Installation & Operation Manual page 60

Ibm 9910 ups 20 kva
Table of Contents

Advertisement

Figure 4 ---2. Remote EPO Control (inside view of cover and bottom of enclosure)
3.
Mount cover to Remote EPO switch enclosure bottom, as shown in
Figure 4---2, for easier wiring.
NOTE: A separate conduit is required for each UPS connected to the Remote EPO
switch.
4.
Install wiring from the Remote EPO switch using ½-in. conduit through the
Customer Interface conduit landing plate on the rear of the UPS cabinet. Refer
to Appendix A, Drawing 164201491---8, for conduit landing area and terminal
board location, and Drawing 164201491---2 for terminal wiring assignments.
5.
Connect the Remote EPO wiring as shown in Tables 4---1 and 4---2 and Figure
4---2.
6.
If you are installing multiple Remote EPO stations, wire additional stations in
series with the first Remote EPO.
4--2
TB2
Powerware 9330 (IBM 9910 20 kVA) Installation and Operation
COVER
TB1
BOTTOM ENCLOSURE
164201491 REV. B 013004

Advertisement

Table of Contents
loading

Table of Contents