3.2

Battery Type

The following battery types are supplied in the UPS Cabinets and external Battery
Cabinets. When purchasing UPS Cabinets or external Battery Cabinets without
batteries, only the following types are recommended. Use of any other battery type
inside Powerware cabinets will void the product warranty. When replacing batteries
use the same manufactuer and part number originally supplied with the unit to
ensure correct harness fit and terminal landing.
Battery Manufacturer
Battery Model
Battery Quantity
3.3

Battery Installation

3.3.1

Installing Internal Batteries in the UPS Cabinet

If the UPS cabinet was ordered without batteries, install the batteries in accordance
with the following procedure.
LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE STEPS IN THIS SECTION.
1.
Ensure that battery breaker CB2 is in the OFF position. If not, set breaker to
OFF position.
2.
Remove left front solid panel and right front vented panel from Powerware 9330
(IBM 9910 20 kVA) UPS. Front panels are secured with magnetic latches and
are removed by pulling panels straight forward to disengage magnetic latches.
3.
Remove screws securing internal safety shield panels and remove panels to
gain access to battery trays.
4.
Remove battery trays, containing wiring and nylon straps, from the UPS
cabinet.
5.
Select batteries in a accordance with paragraph 3.2. Use batteries of the same
age, type, and manufacturer, in each string, so UPS performance is not
affected.
6.
Install four batteries per tray and electrically interconnect the batteries in
accordance with Figure 3---1.
7.
Secure batteries to tray using nylon straps.
8.
Reinstall battery trays into the UPS cabinet.
9.
Connect battery strings in accordance with paragraph 3.4.1.
3--2
CSB Battery
C&D
Technologies, Inc.
Technologies, Inc.
HR12120WFR
UPS12-100FR
24
24
WARNING:
Powerware 9330 (IBM 9910 20 kVA) Installation and Operation
Sterling
HA28---106FR
24
164201491 REV. B 013004