Venting Arrangements Horizontal Termination - Regency P36D-LP10 Owners & Installation Manual

P36d zero clearance direct vent gas fireplace
Hide thumbs Also See for P36D-LP10:
Table of Contents

Advertisement

VENTING ARRANGEMENTS
HORIZONTAL TERMINATION
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems.
Maintain clearances to combustibles.
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever passing through a wall.
RIGID PIPE AND FPI DIRECT VENT SYSTEM (FLEX)
(Propane & Natural Gas)
elbow (two 45
o
Note: FPI Direct Vent Flex System Part #'s
®
Regency
P36D-10 Zero Clearance Direct Vent Gas Fireplace
installation
elbows equal one 90
elbow).
o
o
All Rigid Pipe Systems
4" inner diameter
6-5/8" outer diameter
FPI Flex Vent
4" inner diameter
6-7/8" inner diameter
A vent guard should be used
whenever the termination is lower
than the specified minimum or as
per local codes.
946-515 and 946-516 are only approved
for horizontal terminations.
|
25
|
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P36d-ng10

Table of Contents