The standard delivery includes:
1 x condensate trap (under the burner hood on the
ventilation air pipe)
2 x siphons with 3 condensate hoses and 1 tee (on the
condensate trap)
Condensate connection:
Install condensate trap in the flue outlet of the condensate pan.
Check tightness of the connections.
Install siphons:
Install the first siphon on the connector of the condensate pan.
Install the second siphon on the connector of the condensate
trap.
F i l l t h e s i p h o n s w i t h w a t e r p r i o r t o
commissioning. Otherwise there is a risk of flue
gas escaping.
Connect the condensate hoses of both siphons from the
condensate pan and condensate trap with a tee and connect
to the neutralising system.
Check tightness of the connections.
3063772_201507

14. Fitting the siphons