Step 6 -- Position
and Connect
Controller
Controllers
are ordered separately.
Wired
controllers
should
be installed
in a position
that
maintains good temperature
control:
Position
the thermostat
approximately
48 in. above floor
level.
Do not position
thermostat
where
it can be
directly
affected
by the unit's discharge
airstream.
Avoid external walls and drafts from window
and doors.
Avoid
positioning
near shelves
and
curtains
as these
restrict air movement.
Avoid heat sources
such as direct sunlight,
heaters,
dim-
mer switches,
and other electrical
devices.
WIRELESS
REMOTE
CONTROLLER
-- Before
installa-
tion, operate the remote controller to determine the appropriate
location for reception range. Avoid direct sunlight exposure or
heating
sources. Use proper mounting
screws and controller
bracket to mount the controller
on the wall (see Fig. 11). For
setup instructions,
refer to the controller installation
manual.
ca [Z] cs
REMOTE
CONTROLLER
MOUNTING
SCREWS__ __
REMOTE CONTROLLER
HOLDER
Fig. 11 -- Wireless
Remote Controller
WIRED
REMOTE
CONTROLLER
(PROGRAMMA-
BLE) --
To connect a wired remote controller
(thermostat)
to
the indoor unit, use 4-core shielded cable and 4-pin connector
from electrical
box of indoor unit (see Fig. 12). For setup in-
structions, refer to the controller installation
manual.
INDOOR UNIT
ELECTRICAL
BOX-_
7
I
LL_
CABLE
Fig. 12 -- Wired Remote Controller
(Programmable)
Wiring
WIRED
REMOTE
CONTROLLER
(NON-PROGRAM-
MABLE)
-- To connect wired remote controller
(thermostat)
to the indoor unit, use 5-core shielded cable and 5-pin connec-
tor from unit display panel (see Fig. 13). For setup instructions,
refer to the controller installation
manual.
INDOOR UNIT
ELECTRIC
CONTROL
BOX
N
INDOOR
UNIT
DISPLAY PANEL
5-CORE
CABLE
'_" 5-CORE SHIELDED
CABLE
5-CORE CABLE
WIRED
CONTROLLER
Fig. 13 -- Wired Remote Controller
(Non-Programmable)
Wiring
CENTRAL CONTROLLER--
The central controller is
connected to the indoor unit through outdoor unit with 3-core
shielded cable (see Fig. 14). For setup instructions, refer to the
controller installation manual.
o
o
TO INDOOR
UNIT
i
i
I
L_
24 VAC
X2KE
_
_
FORCED
L EMERGENCY
DAISY cHAi2oT
USED_
sOwN ITCH
sS;IOT% H
Fig. 14 -- Central Controller Wiring