Maintenance; Troubleshooting - Carrier 40WAW007 Installation And Maintenance Instructions Manual

Table of Contents

Advertisement

START-UP
Pre-Start Check
--
Once installation
is complete,
make
the following pre-start checks:
1. All indoor and outdoor units are properly installed.
2. All piping and insulation
is complete.
3. All electrical
connections
(both power and control)
are
properly terminated.
4. All condensate
drams are installed correctly.
5. The power supply is of the right voltage and frequency.
6. The units are properly
grounded
in accordance
with cur-
rent electrical codes.
7. Suction
and liquid line service valves are in open posi-
tion.
System Operation Check
--
Once
the
installation
and pre-start checks are completed,
follow these steps:
1. Using remote controller,
select cooling or heating mode
to check the operation of the system.
2. While the system is m operation,
check the following on
indoor umt:
a.
b.
Switches or buttons on the remote controller are easy to
push.
Indicator light is showing normal operation
and no er-
ror is indicated.
3.
c. Swing mode of air louvers is working (if applicable to
unit).
d. Dram pump operation is normal (if applicable).
e. No abnormal vibration or noise is noticed.
While the system is m operation, check the following on
outdoor unit:
a. No abnormal vibration or noise is noticed.
b. Condenser fan is in operation.
c. Indicator light is showing normal operation and no er-
ror is indicated.
NOTE: If the unit is turned off or restarted, there is a time
delay of 3 minutes for the compressor to start from the time the
power is restored.
MAINTENANCE
When
servicing
or repairing
this unit, use only factory-
approved
service replacement
parts.
Refer to the rating
plate on the unit for complete
unit model number,
serial
number and company
address. Any substitution
of parts or
controls not approved by the factory will be at the owner's
risk and may result in equipment
damage.
To avoid equipment
damage, do not attempt to reuse any
mechanical
or electrical
controllers
that have been wet.
Replace defective controller.
EVERY 3 MONTHS:
Check the air filter condition.
Clean or replace
if neces-
sary.
EVERY 6 MONTHS
-- Follow 3-month maintenance
sched-
ule. In addition:
Clean condensate
tray with suitable
cleaning
agent.
Clean the grille and panel.
EVERY
12 MONTHS
--
Follow
6-month
maintenance
schedule. In addition:
Be sure all electrical
connections
are secure.
Check condensate
pump operation.
Check
the heating
and cooling
action
to confirm
proper
operation.
TROUBLESHOOTING
Figure
15 shows
shows
the LED
display
panels
for
40WAW007-018
and 40WAW024
units.
See Table 3 for a
smmnary of display indicators.
Table 4 lists problems, possible
causes, and possible solutions.
TIMER
OPERATION
TIMER
40WAWO07-O 18
OPERATION
40WAW024
Fig. 15 -- 40WAW LED Display Panel
DEE/FAN
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

40waw00940waw01240waw01540waw01840waw024