Refrigerant Piping - Carrier 40WAW007 Installation And Maintenance Instructions Manual

Table of Contents

Advertisement

LEFT PIPING
LEFT BACK PIPING
RIGHT BACK PIPING
RIGHT PIPING
Fig. 8 -- Condensate Pipe Routes
REFRIGERANT PIPING
When connecting
from an indoor unit to an outdoor unit,
the isolation valve at the outdoor unit should be in closed
position
throughout
the refrigerant
piping process. Failure
to follow this procedure may result in equipment
damage.
When connecting
from an indoor unit to an outdoor unit,
follow these procedures:
Check
maximum
height
drop and length
of refrigerant
piping between
the indoor
and outdoor
unit. If the differ-
ence between them is more than 33 ft, consider mounting
the outdoor
unit above indoor unit.
Refrigerant
piping
connection
between
indoor
and out-
door
units
should
be performed
once
the
units
are
secured
at their respective
installation
locations.
The refrigeration
piping starts at the indoor unit and ends
at the outdoor
unit.
The number
of bends in the refrigeration
piping
must be
fewer than 15.
The refrigerant
piping
should be dry and free of dust and
other impurities.
The bending
angle
of the refrigerant
pipe
should
not
exceed
90 degrees
and the bending
radius
should
be as
large as possible
to prevent
any breakage
in piping.
Use proper cutting and flaring tools to avoid leakage.
Before
insulating
the suction
and
liquid
refrigeration
pipes, perform
pressure
and leak tests.
For details,
see
the outdoor unit installation
manual.
Insulating
both suc-
tion and liquid refrigerant
pipes is recmmnended.
Vacuuming
and charging
of the system
should be carried
out as described
in the outdoor
unit installation
manual.
Step 5 -- Complete
Electrical
Connections
Installation
of wiring must conform
with local building codes
and with National
Electric
Code ANSI!NFPA
70, latest edi-
tions. Units must be electrically
grounded
in conformance
with
the code. In Canada,
wiring must comply
with CSA C22.1,
Electrical Code.
All units must be wired strictly in accordance with the wir-
ing diagram furnished with the unit. Any wiring different
from the wiring diagram could result in personal injury and
property damage.
Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature rat-
ing of at least 105 C.
Ensure supply voltage to the unit, as indicated on the serial
plate, is not more than 10% over the rated voltage or 10%
under the rated voltage.
Failure to follow these recolnmendations may result in
equipment damage.
This equipment in its standard form is designed for an elec-
trical supply of 208/230-1-60. Any damage to or failure of
units caused by incorrect wiring or voltage is not covered by
warranty.
Electric wiring must be sized to carry the full load amp
draw of the motor, starter, and any other controls that are used
with the unit. See Table 2 for electrical data.
Table 2 -- 40WAW Electrical Data
UNIT
40WAW007
40WAW009
40WAW012
40WAW015
40WAW018
40WAW024
LEGEND
MCA
-- Minimum Circuit Amps
MOPD -- Maximum Overcurrent
Protective Device
POWER SUPPLY
MCA
MOPD
02
15
02
15
02
15
0,3
15
0,3
15
0,6
15
C
JS
After the pipe work is complete,
the electrical
supply can be
connected
by routing the cable through the appropriate
casing
holes or knockouts
and connecting
the supply
and ground
cables to the unit's power terminal.
Be sure the power wiring and control wiring do not cross, as
this might cause disturbance
on the controls side. See Fig. 9
and 10 for wiring diagrams.
Electrical shock can cause personal
injury and death. Dis-
connect power supply before making wiring connections.
There may be more than one disconnect
switch. Tag all dis-
connect locations to alert others not to restore power until
work is completed.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

40waw00940waw01240waw01540waw01840waw024

Table of Contents