To Use the Vent Graph (Figure 20)
1. Determine the height of the center of the horizontal vent
pipe. Using this dimension on the Sidewall Vent Graph,
locate the point it intersects with the slanted graph
line.
2. From the point of this intersection, draw a vertical line to
the bottom of the graph.
3. Select the indicated dimension, and position the unit in
accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 35 feet,
the horizontal run to the outer wall flange must not exceed
6.5 feet.
EXAMPLE B:
If the vertical dimension from the floor of the unit is 6.5 feet,
the horizontal run to the outer wall flange must not exceed
14.5 feet.
Special Note: For each 45 degree elbow installed in the
horizontal run, the length of the horizontal run MUST be
reduced by 18" (45cm). This does not apply if the 45 degree
elbows are installed on the vertical part of the vent system.
Reduce 3' for every 90° elbow.
Example: According to the chart the maximum horizontal
vent length is 20' and if two 45 degree elbows are required
in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per
side wall installation is two (2). These elbows can be installed
in either the vertical or horizontal run.
Note: On vertical venting the first elbow does not get
counted.
Note: Flue heat shield must be installed for venting applications
with less than two feet of vertical pipe off the top of the
fireplace.
28653-2-0811

VENTING FIREPLACE - TOP

FLUE HEAT
SHIELD
REQUIRED
TOP VENT
CONNECTION
Venting Graph (Dimensions in Feet)
TOP EXIT - VERTICAL AND HORIZONTAL TERMINATION
(DIMENSIONS IN FEET)
HORIZONTAL RUN
Acceptable vertical and horizontal vent run.
(40' maximum vertical and 20' maximum horizontal)
Unacceptable vertical and horizontal vent run.
Figure 20
Page 15